After a Sound Velocity Calibration, this value represents the actual sound.
The velocity of sound in water is typically 1483 m/s (4864 ft/s).
The units used are m/s if P005 = 1, 2, or 3 (or ft/s if P005 = 4 or 5).
Values:

Temperature Compensation Parameters (P660 to P664)

P660 Temp Source
This feature is preset to "AUTO". On scanning a transducer, the DPS300 scans
the TS-3 temperature sensor assigned to the transducer. If a TS-3 sensor is not
connected, the temperature measurement from the transducer is used.
If the wastewater temperature between the transducer and the sludge varies,
connect a TS-3 Temperature Sensor between these two points and select
"average".
Values:
1 = AUTO
2 = Temp Fixed
3 = XCT-12 Transducer
4 = TS-3 Temperature Sensor
5 = Average
6 = TS-3 SENSOR # 1
P661 Temp Fixed
Use this feature if a temperature sensing device is not used.
Enter the temperature (in °C) of the clarifier wastewater. If the temperature varies
with distance from the transducer, enter the average temperature. This value is
preset to 20.00°C.
Values:
P662 Temperature Sensor Allocation
As preset, TS-3 number 1 and 2 are allocated to Point Number 1 and 2
respectively.
To alter this allocation, enter the TS-3 number which is used for the distance
calculation of the Point Number displayed.
When both TS-3 temperature sensors are allocated to one Point Number, the
temperature measurements from each sensor are averaged for that clarifier.
Values:
1 = TS-3 number 1
2 = TS-3 number 2
1.2 = TS-3 number 1 and 2 average
InterRanger DPS300
50.00 to 2000 m/s (164.0 to 6562 ft/s)
-50 to 150
74
7ML19981BC01