Relay Parameters (P100 To P104, P110 To P113, P129) - Siemens interranger DPS300 Instructional Manual

Table of Contents

Advertisement

Relay Parameters (P100 to P104, P110 to P113, P129)

If relays are to be used, alter the following parameters as required.
Note:
Otherwise, proceed to mA OUTPUT PARAMETERS.
Relays may be programmed as Standard Alarms or for Custom Relay operation.
For Standard Alarms (relays operate based on sludge level), select the Relay Set
Up (P100) desired and alter the Standard Alarm (P101 to P104) parameters as
required, before proceeding to Relay Failsafe (P129).
For Custom Relay operation, select the Relay Set Up (P100) which most closely
matches your requirements, and alter the Custom Relay Parameters (P110 to
P113) as required, before proceeding to Relay Failsafe.
P100 (G) Relay Set Up
This parameter presets relays to operate as Standard Alarms. The Relay
Allocation (relay / point number association) and Standard Alarm (P101 to P104)
parameters are also preset.
Relay status during a measurement difficulty is dependent upon Failsafe
programming. See Failsafe Parameters (P070 to P072) and Relay Failsafe
(P129). As preset, relay status is "held" at "last known" sludge levels until a valid
measurement is made.
Option
InterRanger DPS300
Relay #
1
1
2
3
4
2
1
2
3
4
3
1
2
3
4
4
1
2
3
4
58
Point #
Standard Alarm (as % of Span,
1
(High Alarm) P101 = 80.00%
1
(Low Alarm) P102 = 20.00%
2
(High Alarm) P101 = 80.00%
2
(Low Alarm) P102 = 20.00%
1
(High Alarm) P101 = 80.00%
1
(High High Alarm) P103 = 90.00%
2
(High Alarm) P101 = 80.00%
2
(High High Alarm) P104 = 10.00%
1
(Low Alarm) P102 = 20.00%
1
(Low Low Alarm) P104 = 10.00%
2
(Low Alarm) P102 = 20.00%
2
(Low Low Alarm) P104 = 10.00%
1
(High Alarm) P101 = 80.00%
1
(Low Alarm) P102 = 20.00%
1
(High High Alarm) P103 = 90.00%
1
(Low Low Alarm) P104 = 10.00%
P007)
7ML19981BC01

Advertisement

Table of Contents
loading

Table of Contents