Installation shall only be performed by qualified personnel, and in accordance with
local governing regulations.

Location

Electronics
Although the Mounting Assembly provides a mounting plate for external
installation, the unit can also be installed indoors in a controlled environment
comfortable to operating personnel.
If it is required to mount the unit outdoors, the supplied panel can be attached to
the Mounting Assembly.
Regardless, the unit must be mounted in an area that:
is conformant to the units specifications
provides clearance to swing open the front cover and perform the required wiring
connections
provides access for viewing
is vibration free
Avoid a location that is:
exposed to continuous direct sunlight. (Otherwise, provide a sun shield.)
close to high voltage or current runs, contactors, or SCR control drives
Cable/Conduit Entry Requirements
Determine the number of conduit entries required:
transducer(s) – one or two transducers
communications – SmartLinx, RS-485, RS-232, bi-polar
instrumentation – relay outputs, 4-20 mA
synchronization – if more than one unit in proximity
power
Note:
Transducer cables must be run in a grounded metal conduit, separate from
other wiring, (except TS-3 temperature sensor wiring, if applicable).
This product is susceptable to electrostatic shock. Follow proper grounding
procedures.