Level System Synchronization

Avoid mounting the DPS300 near another ultrasonic level monitor. Likewise, when
more than one monitor is installed within a single plant/facility, ensure the
transducer cables of each system are run in separate grounded metal conduits. If
this system separation is impractical, or despite separation efforts measurement
difficulties are encountered, system synchronization may be required.
Note:
To synchronize the DPS300 with other Siemens ultrasonic level monitors contact
Siemens or your local distributor.

Power

Before making the power connection, ensure that
the proper voltage selection is set.
The voltage selection switch is shown in the off
position. Select the appropriate voltage.
Notes:
InterRanger DPS300
The equipment must be protected by a 15 A fuse or circuit breaker in the
building installation.
A circuit breaker or switch in the building installation, marked as the
disconnect switch, shall be in close proximity to the equipment and within easy
reach of the operator.
Never operate the DPS300 with the enclosure lid open, or with the ground
(earth) wire disconnected.
Ensure that any associated alarm or control equipment is disconnected until
satisfactory operation is verified.
40
100 / 115 / 200 / 230, 50 / 60 HZ
select voltage via switch above
7ML19981BC01