Display Scaling; Remote Display Troubleshooting Icons - Siemens 9810 Series User Manual

Power meter
Hide thumbs Also See for 9810 Series:
Table of Contents

Advertisement

Display scaling

Configuring display units scaling using ION Setup

Remote display troubleshooting icons

110
You can customize the units for metered values shown on the display and
webpages.
You can configure the units for voltage, current, power and energy values shown
on the display and webpages from their default units, and you can set the
resolution for the display. To identify which values will have the modified units,
refer to the display and web units information in your meter's Modbus map,
available from www.usa.siemens.com/pds.
You can customize the units for metered values shown on the display and
webpages using ION Setup.
Configuring display units scaling is an advanced procedure that requires in-depth
knowledge of your meter, its underlying architecture, and the system in which it is
installed.
To identify which values will have the modified units, refer to the display and web
units information in your meter's Modbus map, available from
www.usa.siemens.com/pds.
NOTE: Custom units and resolution settings are automatically adjusted for
current and voltage values to help prevent your meter's display from showing
incorrect zero values.
1. Start ION Setup.
2. Connect to your meter in advanced mode.
3. Navigate to the Display Options Modules folder and double-click on the
module in the righthand pane.
The Display Options screen is displayed.
4. Select the Setup Registers tab.
5. Select the display units you want to configure: Voltage Units, Current Units,
Power Units or Energy Units. Click Edit.
A unit selection screen is displayed.
6. Select the desired units from the dropdown list, and click OK.
7. When you have finished configuring the display units, click Send to send your
changes to the meter and close the Display Options screen.
See the ION Reference, available from www.usa.siemens.com/pds, for more
information about the Display Options module and your meter's ION
architecture.
The remote display shows troubleshooting icons in addition to the meter's status
LED information.
Icon
Description
Your remote display is connecting to your meter.
Your remote display cannot communicate to your meter. Check the
connection between your meter and the display. Check the meter's
status LED to confirm that the meter is operating normally.
Display