Configuring onboard digital inputs using ION Setup
Configuring option module digital inputs using ION Setup
78
Related Topics
Configuring time information using ION Setup
You can use ION Setup to configure your meter's digital inputs.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to Onboard I/O > Digital Inputs. The tabs correspond to each
digital input. Click on the tab for the digital input you want to edit.
4. Configure the digital input by selecting the parameter and clicking Edit.
5. Once the parameter has been configured, click OK to save the setting to the
meter.
Parameter
Value/range
Input Mode
Pulse, KYZ, A/C,
IRIG-B
Polarity
Inverting/Non-Inverting
Debounce
0.000 - 1.000
Assigned Port
Defined by your meter's
hardware
EventLog Mode
Log Off/Log On
State
OFF/ON
1
IRIG-B can only be connected to one of the onboard digital inputs, not an option module. You
must also configure your meter's clock to use IRIG-B time synchronization.
You can configure option module digital inputs using ION Setup.
Digital inputs are available on your meter. You can add more digital inputs using
optional I/O modules.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to Expansion Modules > Option I/O Modules and select the
module tab that corresponds to the option module with the digital input you
want to configure.
4. Select the digital input channel and click Edit.
The setup screen for that digital input is displayed.
5. Configure the digital input by selecting the parameter and clicking Edit.
Description
Specifies how the meter processes the
signal:
1
Pulse: the meter counts an entire pulse
(from off-on to on-off) as one input.
KYZ: the meter counts a transition
(from off-on or from on-off) as one input.
A/C: the meter detects analog signals
where the ON condition is based on the
presence of an AC signal
IRIG-B
time synchronization signal.
Specifies if the signal from the digital port is
inverted or not inverted.
Specifies how long (in seconds) the signal
must remain in a state to be considered a
valid state change.
Your meter's physical digital input port.
Specifies if events generate log entries.
Indicates the status of the digital input.
Inputs / outputs
1
: the meter detects an IRIG-B
7EN05-0390-00