Logging

Log depth configuration

Log interval configuration

Log mode configuration

7EN05-0390-00
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to the Logging > Memory screen.
The Status tab:
lists the default logs, their interval (Duration) and depth (Records), if
applicable, and the percentage of available memory used by the log.
provides information on how much of the meter's memory is used for
system tasks in the System Resources list item.
displays the total meter memory and the percentage of memory in use
versus memory available.
You can change the number of records (depth) stored in the log.
Use ION Setup to change the maximum number of records (depth) stored in the
log in the meter's long-term memory.
Data logs and circular-format waveform recorders have a minimum depth of 1
record. The maximum depth is dependent on your meter's memory and the
configuration of your other logs.
You can configure the logging interval, which is how frequently records are logged.
You can change the logging intervals for most logs using the ION Setup Assistant
Logging > Memory screen.
Changing the interval for other logs (for example, logs that are related to
standards or triggered by disturbances) is an advanced procedure that involves
using the Advanced mode of ION Setup to modify settings in the module that is
linked to the log's Record input. See the ION Setup help and the ION Reference
for more information.
Programming your meter to write to any data recorder at continuous intervals
shorter than 60 seconds (heavy logging configuration) can cause loss of data in
the event of a power failure.
DATA LOSS
Failure to follow these instructions can result in data loss.
Use an uninterruptible power supply (UPS) if you program your meter for heavy
logging.
You can configure the log record mode, or how the log behaves when full.
Changing how the log records information (circular or stop-when-full) is an
advanced procedure that requires changing the RecordMode setup register in the
Data Recorder and Waveform Recorder modules.
NOTICE
169