Energy pulsing

Default energy pulsing LED sources

84
5. Configure the digital output by selecting the parameter and clicking Edit.
Parameter
Value/Range
Source
Digital/Boolean
Force ON
Pulse
Force OFF
1
Pulse
Normal
1
Pulse
EventLog Mode
Log Off/Log On
Polarity
Inverting/non-
inverting
PulseWidth
0 - 2,000,000
Port
1
These parameters are only valid when pulse width is set to 0.
Related Topics
Option I/O modules configuration
You can configure the meter's energy pulsing LEDs or onboard digital outputs for
energy pulsing applications.
When an LED or output is set to energy pulsing, the meter sends a readable pulse
or signal based on the measured energy source value. This pulse can be used for
accuracy verification or as an input to another energy monitoring system.
Your meter's energy pulsing LEDs have default energy source values configured
for accuracy verification testing.
For LED locations, see your meter's installation guide.
LED
kVARh pulse LED
kVARh pulse infrared LED
kWh pulse LED
kWh pulse infrared LED
NOTE: The energy pulsing LEDs are configured in pairs. For example,
changing the energy source value will change it for both the regular and
infrared kVARh LEDs.
NOTE: To modify your default energy source value, go into the advanced
mode of ION Setup and modify the associated Calibration Pulser module. This
is an advanced procedure that should only be performed if you have advanced
knowledge of ION and the power system your meter is connected to.
Description
Link this input to the value that drives the state of the
digital output.
If Source is not linked, the digital output state is driven
by the Force ON, Force OFF values.
Link this input to a pulse that forces the digital output
on for the PulseWidth duration, regardless of the
Source input.
Link this input to a pulse that forces the digital output
off.
Pulsing this input will switch the driver of the digital
output from Force ON to Source.
Specifies if events generate log entries.
Specifies if the signal to the digital port is inverted or
not inverted.
Specifies the duration of the pulse, in seconds.
Setting this parameter to 0 sets the digital output
continuously on.
The physical digital output port connection. Only
available ports are shown.
Default energy pulsing source
kVAR del+rec
kW del+rec
Inputs / outputs
7EN05-0390-00