Communications Protocol Lockout Overview - Siemens 9810 Series User Manual

Power meter
Hide thumbs Also See for 9810 Series:
Table of Contents

Advertisement

Communications protocol lockout overview

= Logged event
= Lockout event
= Invalid login attempt
= Valid login attempt
T
= Time (minutes)
0 0 1
= Counter of invalid attempts
Scenario 1
User repeatedly enters the
same incorrect password to
attempt access to the meter
Scenario 2
User enters different
passwords to attempt access
to the meter
116
The communications protocol lockout security feature allows you to set the
number of invalid login attempts that each user can make using a particular
protocol and communications method before being locked out (a user is defined
as a user login and password combination).
For protocols that are not session-based (ION), you can configure how often the
device registers invalid login attempts by configuring the session timeout. You can
also configure the lockout duration for all configurable protocols.
Session timeout specifies the active duration for a protocol; during this time,
repeated invalid login attempts using the same USER/password combination are
not registered (repeated invalid attempts with different combinations are still
registered). Session timeout only applies to protocols which are not session-based
(ION) and send credentials with each packet, and should be configured to help
prevent accidental lockouts and filling the meter's event log with protocol access
events
NOTE: If protocol lockout is set to 0 (zero) there is no limit to the number of
invalid login attempts and the protocol will never be locked out. However, the
invalid login attempt events are recorded if the meter is configured to record
invalid access attempts.
User1 valid password = 11
User2 valid password = 22
T=0
0 0 1
User1
pw = 23
T=0
0 0 1
User1
pw = 0
Once a user is locked out, the device will not accept login attempts from that user
on that protocol and communications method until the lockout duration has
passed. Invalid login attempts accumulate until the user has completed a valid
login or is locked out. If the user enters the correct USER/password combination
before being locked out, the invalid attempt counter is reset to zero. Even if the
user is locked out using ION over Ethernet, that user can still access the device by
entering the correct USER/password combination over a different protocol and
communications method.
Lock attempts = 3
Lockout duration = 1440 minutes
T=10
0 0 1
User1
pw = 23
T=10
T=22
0 0 3
0 0 2
User1
User1
pw = 3
pw = 4
T=32
T=65
T=45
0 0 2
User1
User2
pw = 23
pw = 22
T=45
User2
pw = 22
7EN05-0390-00
Security
0 0 3
User1
pw = 23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Us2:9810tcUs2:9810rc