Device Connections

Symbio 500 controller supports the following device connections:
Table 1. Device connections
Quan-
tity
Connection
Analog Input (AI1 to
5
AI5))
Universal input (UI1
2
and UI2)
Binary input (BI1 to
3
BI3)
Binary Outputs
(BO1 to BO3)
3
Binary Outputs
(BO4 to BO9)
6
Analog Output /
Binary Input (AO1/
BI4 and AO2/ BI5)
2
Pressure Inputs
2
(PI1 and PI2)
Point total
23

Expansion Modules

The Symbio 500 controller has 23 on-board points. The controller can be point-expanded by using
expansion modules. The Symbio 500 can have an additional 110 points, for a total of 133 points
BAS-SVX090B-EN
Types
Range
10kΩ – Type II, 10kΩ – Type
III, 2252Ω – Type II, 20kΩ –
Thermistor
Type IV, 100 kΩ
RTD
Balco™ (Ni-Fe) 1kΩ, 385 (Pt)
1kΩ, 375 (Pt) 1kΩ, 672 (Ni)
1kΩ,
Setpoint
189Ω to 889Ω
(Thumbwheel)
Resistive
100Ω to 100kΩ
Linear Current
0–20mA
Linear Voltage
0–10Vdc
10kΩ – Type II, 10kΩ – Type
III, 2252Ω – Type II, 20kΩ –
Thermistor
Type IV, 100 kΩ
Balco™ (Ni-Fe) 1kΩ, 385 (Pt)
1kΩ, 375 (Pt) 1kΩ, 672 (Ni)
RTD
1kΩ,
Setpoint
189Ω to 889Ω
(Thumbwheel)
Resistive
100Ω to 100kΩ
Binary
Dry contact
Pulse Accumulator
Solid state open collector
24 Vac detect
Form C Relay
0.5A @ 24Vac pilot duty
0.5A @ 24Vac resistive and
pilot duty
Triac
Linear Current
0 - 20mA
Linear Voltage
0 - 10Vdc
Binary Input
Dry contact
Pulse Width
80 Hz signal @ 15Vdc
Modulation
0 - 5 In H20
Notes
These inputs can be configured for timed override capability.
Supports *, ** for Trane Zone Sensors.
Typically used for fan speed switch.
These inputs may be configured to be thermistor or resistive inputs,
0– 10 Vdc inputs, or 0–20 mA inputs.
Low impedance relay contact.
Minimum dwell time is 25 milliseconds ON and 25 milliseconds OFF.
The controller provides the 24Vac that is required to drive the binary
inputs when using the recommended connections.
Ranges given are per contact. Power needs to be wired to the binary
output. All outputs are isolated from each other and from ground or
power.
Note: Class 1 voltages shall not be used on Symbio 400–B/500
controllers.
Ranges given are per contact and power comes from the TRIAC
SUPPLY circuit. Use for modulating TRIACs. User determines
whether closing high side (providing voltage to the grounded load) or
low side (providing ground to the power load).
Each termination must be configured as either an analog output or
binary input.
Pressure inputs supplied with 5 volts (designed for Kavlico™
pressure transducers).
General Information
11