Siemens FS720 Mounting & Installation page 97

Fire detection system
Table of Contents

Advertisement

6.11.2.2 X4 remote transmission /release element
Pin
Designation
6
+24V
5
↑ UE Alarm+
4
UE Alarm-
3
UE Rueckm
2
FSE+
1
FSE-
Building Technologies
Fire Safety
Description
Operating voltage (+24 V)
↑ Remote transmission/device alarm (+)
Remote transmission/device alarm (-)
Remote transmission /device acknowledgement (+)
Release element with monitored remote switching output or separately monitored
key switch
Admissible cable cross-section: 0.2...1.5 mm²
X4
+
UE Alarm +
+
-
UE Alarm -
UE Rueckm
+
-
FSE -
ST Fault contact of the transmission device
Installing, exchanging and connecting modules
Fire brigade periphery module [DE]
6
5
200 ... 2k
Ω
Ω
4
3
2
680
1
ST
Ω
3.3kΩ
A6V10210390_j_en_--