3.5.4
Fire brigade periphery module
FCI2001-D1
3.5.5
Sounder module
FCA2005-A1
2 mounting feeds
3.5.6
Network module (SAFEDLINK)
FN2001-A1
Building Technologies
Fire Safety
Fire brigade periphery module
Application
For VdS compliant switching to fire department periphery devices (for Germany).
Features
The module has connections for FBF, FSD, ÜE, FSE, ÖA, KL, tamper alarm FSD.
Mounted in the housing on the mounting plate FHA2007-A1, or on the back wall of the housing.
–
Technical data
Operating voltage
Operating current
Connection terminals VdS peripheral devices
Connection terminals for power supply
Dimensions (W x H x D)
Sounder module
Application
With the sounder module it's possible to split up a collective horn line on 4 lines. Each of this line
controls and monitored each individual sounder. 2 sounder modules can be used, but condition is a
cascading of both.
The sounder module can be mounted onto the mounting plate FHA2007-A1 or onto the U-rail TS35 in
–
control panel with the enclosed mounting feeds.
Technical data
Operating voltage
Operating current
Quiescent current
Supervised output
Cable capacity
Humidity
Color housing / cover
Dimensions (W x H x D)
Network module (SAFEDLINK)
Application
To network multiple stations C-WEB/SAFEDLINK.
Plugged into the back side of the operating unit.
–
Technical data
Connection terminals
Dimensions (W x H x D)
Networkable fire control panels
Part no.
A5Q00013100
21...28.6 VDC
max. 1.6 A
2
0.2...1.5 mm
2
0.5...2.5 mm
150 x 190 x 40 mm
Part no.
A5Q00014866
21...28.6 VDC
Max. 2 A (fused with 2 AT)
20 mA
4 x 1 A
2
0,08...1,5 mm
≤95 % rel. rel.
pure white, RAL 9010 / transparent matt
132 x 90 x 24 mm
Part no.
A5Q00012851
2
0,2...2.5 mm
50 x 20 x 70 mm
A6V10227652_i_en_--
2016-05-30
17