Pin Assignments - Siemens FS720 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

6.26.2 Pin assignments

6.26.2.1 X1 switching contacts relays 1...5
Building Technologies
Fire Safety
Mounting steps
1. Mount the RT interface (4) to the mounting plate (2) or the rear panel (observe
correct installation position) as shown using the five fixing screws (3). The five
spacer bolts (1) must be used when installing on the mounting plate.
2. Wire up the RT interface according to the pin assignment.
3. Fix the cables with the enclosed, self-adhesive Panduit bases and the cable
ties. One means of fixation may be e.g. for the mounting plate and the other for
the rear panel of the station.
Pin
Designation
10
REL1_OUT+
9
REL1_OUT-
8
REL2_OUT+
7
REL2_OUT-
6
REL3_OUT+
5
REL3_OUT-
4
REL4_OUT+
3
REL4_OUT-
2
REL5_OUT+
1
REL5_OUT-
NO = Normally open
NC = Normally closed
Admissible cable cross-section: 0.14...1.5 mm²
REL1_OUT+
REL1_OUT-
REL2_OUT+
REL2_OUT-
REL3_OUT+
REL3_OUT-
REL4_OUT+
REL4_OUT-
REL5_OUT+
REL5_OUT-
Installing, exchanging and connecting modules
Description
Relay 1 switching contact (configurable as NO or NC)
Relay 1 switching contact
Relay 2 switching contact (configurable as NO or NC)
Relay 2 switching contact
Relay 3 switching contact (configurable as NO or NC)
Relay 3 switching contact
Relay 4 switching contact (configurable as NO or NC)
Relay 4 switching contact
Relay 5 switching contact (configurable as NO or NC)
Relay 5 switching contact
X1
10
9
8
7
6
5
4
3
2
1
6
RT interface [NL]
181 | 222
A6V10210390_j_en_--
2015-12-15