6.24.2.3 X3 sounder 3 and 4 outputs
Building Technologies
Fire Safety
Pin
Designation
1
S4 out+
2
S4 out-
3
S3 out+
4
S3 out-
Admissible cable cross-section: 0.08...1.5 mm²
X3
S4 out+
1
+
S4 out-
2
-
+
S3 out+
3
-
S3 out-
4
The terminating resistor of 3 kΩ has to be connected even when the output is not in
use.
Installing, exchanging and connecting modules
Description
Sounder output 4 (+)
Sounder output 4 (-)
Sounder output 3 (+)
Sounder output 3 (-)
3
3
6
Sounder module