Connecting The Safety Module Fn2009 - Siemens FS720 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

6.14.4.3 Connector strip for detector contact

6.14.5 Connecting the safety module FN2009

6.14.5.1 Connector strip for supply
6.14.5.2 Connector strip for detector contact
Building Technologies
Fire Safety
The detector contact is a potential-free relay contact which can be used to report
error states by interrupting contact.
The following errors can be signaled by the detector contact:
Loss of a link on a monitored port
Failure of a redundant source of voltage
Incompatible C-plug inserted
The detector contact remains activated until the error is rectified or until the current
status is adopted by the button as the new nominal status.
The detector contact is always activated (opened) by switching off the FN2008-A1.
Pin
Designation
1
F1
2
F2
Pin
Designation
1
L1+
2
M1
3
M2
4
L2+
The L1+/M1 and L2+/M2 connections are designed for redundant supply and are
not plated-through. Use of the redundant L2+/M2 supply inputs is optional and not
necessary for EN-54 compatibility.
The detector contact is a potential-free relay contact which can be used to report
error states by interrupting contact.
The following errors can be signaled by the detector contact:
Error in voltage supply
Internal error
The detector contact remains activated until the error is rectified.
The detector contact is always activated (opened) by switching off the FN2009-A1.
Pin
Designation
1
F1
2
F2
Installing, exchanging and connecting modules
Ethernet switch FN2008 and safety module FN2009
Description
Detector contact 1
Detector contact 2
Description
Supply input 1 (+DC 24 V)
Supply input 1 (DC 0 V)
Redundant supply input 2 (DC 0 V), optional
Redundant supply input 2 (+DC 24 V), optional
Description
Detector contact 1
Detector contact 2
6
121 | 222
A6V10210390_j_en_--
2015-12-15