Installing, exchanging and connecting modules
6
Periphery board (4 loops)
6.3.2.4 X7 RT alarm and RT fault changeover contacts
58 | 222
Building Technologies
Fire Safety
Pin
Designation
6
FAU_NC
5
FAU_COM
4
FAU_NO
3
AL_NC
2
AL_COM
1
AL_NO
Admissible cable cross-section: 0.2...1.5 mm²
1
Remote transmission
FAU_...
Diagram of relay in ↑ normal operation = contact 5/4 closed
AL_...
Diagram of relay in normal operation = contact 2/3 closed
Description
↑ RT fault ↑ normally closed contact
RT fault center tap (common)
RT fault ↑ normally open contact
RT alarm break contact (normally closed)
RT alarm center tap (common)
RT alarm make contact (normally open)