5 Mounting and assembling a station

5.1 Install rear panel

5.1.1 Surface mounting

Building Technologies
Fire Safety
Mounting instructions
Any surface irregularities can be compensated with washers or wooden wedges.
The rear panel is attached to the wall using screws with a diameter of 6 mm.
The supplied edge protection strip must be placed around rectangular breakout
openings.
Depending on the cable type, up to max. eight cables can be fed through each
round breakout opening (20 mm with rubber grommet).
Only one cable may be fed through each screwed cable gland (not within the
scope of delivery).
Mounting steps
WARNING
Electrical voltage
Electric shock
The mains supply may only be connected by an expert.
WARNING
Heat bridge between the station and mounting surface caused e.g. by
overheating of the batteries
Danger of fire
If you mount the station on a flammable wall, all cut-out sections for the
mounting holes must be sealed using the supplied aluminium stickers.
1. Break out the required cable openings on the rear panel. Signal and control
cables must be fed into the housing from above or from the rear (EMC
protection).
2. Screw in the cable gland for the mains cable (Ø 20 mm), or insert a rubber
grommet.
3. Mark the bore holes for the dowels using the supplied drilling template. The
cardboard cover in the packaging is also the drilling template. The holes in the
cardboard cover correspond to the fixing holes in the rear panel. You can also
mark the holes based on the specifications provided in the product insert.
4. Drill the holes and insert the supplied dowels.
5. Attach the housing using the supplied screws.
6. Stick the supplied aluminium stickers over all holes for wall mounting.
7. Feed the mains cable into the housing and fix the cable with cable ties.
8. Protect the electronics if necessary using the cover of the packaging or other
suitable means.
Mounting and assembling a station
Install rear panel
A6V10210390_j_en_--
5