Wiring
6.6 Connecting cable shields
Procedure
To connect the cable shield, follow these steps:
Table 6-5
Mounting the shield contact
Step
Procedure
1
If necessary, connect the supply voltage L+ and M on the terminal
block.
Holder
Supply voltage L+, M
2
Press the shield contact up into the holder until you hear it click into
place.
Shield contact
Flat connector for push-on contact (6.3 × 0.8 mm)
3
● Remove the cable insulation material around the shield terminal.
● Connect the cable to the terminal block and insert the cable into
the shield contact.
Insulating material removed (approx. 20 mm)
Cable to sensor/actuator
92
Illustration
ET 200SP HA Distributed I/O system
System Manual, 08/2019, A5E39261167-AD