Shipping And Storage Conditions - Siemens SIMATIC ET 200SP HA System Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Technical specifications

9.3 Shipping and storage conditions

9.3
Shipping and storage conditions
Introduction
The ET 200SP HA distributed I/O system surpasses requirements for transport and storage
conditions according to IEC 61131‑2. The following information applies to modules that are
shipped and/or stored in their original packaging.
Table 9-9
Type of condition
Free fall (in shipping package)
Temperature
Air pressure
Relative humidity
Sinusoidal oscillations according to
IEC 60068-2-6
Impact according to IEC 60068-2-27
Note that I/O modules with relay contacts are only suitable for an elevation up to 3000 m (corresponds
1)
to air pressure of around 690 hPa).
142
Shipping and storage conditions for modules
1)
Permissible range
≤1 m
From -40 °C to +70 °C
From 1080 hPa (corresponds to a depth of approx. -1000 m)
Up to 606 hPa (corresponds to an elevation of approx. 4000
m)
5% to 95%, without condensation
5 - 8.4 Hz: 3.5 mm
8.4 - 500 Hz: 9.8 m/s
2
250 m/s
, 6 ms, 1000 shocks
2
System Manual, 08/2019, A5E39261167-AD