Siemens SIMATIC ET 200SP HA System Manual page 139

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Sinusoidal disturbance variables
The following tables show the electromagnetic compatibility of the ET 200SP HA distributed I/
O system to sinusoidal interference.
Table 9-3
HF radiation according to IEC 61000-4-3/NAMUR NE21
Electromagnetic RF field, amplitude-modulated
80 MHz to 2.0 GHz
10 V/m
80% AM (1 kHz)
Table 9-4
RF coupling in accordance with IEC
61000-4-6
(10 kHz) 150 kHz to 80 MHz
10 V
80% AM (1 kHz)
Table 9-5
Magnetic field according to IEC
61000-4-8
50/60 Hz 100 A /m
50/60 Hz 1 kA/m for 1 s
Table 9-6
Test according to IEC 61000-4-16
10 V
100 V for 1 s
ET 200SP HA Distributed I/O system
System Manual, 08/2019, A5E39261167-AD
HF radiation - sinusoidal interference
HF coupling - sinusoidal interference
unmodulated
rms
Magnetic field IEC 61000-4-8
Voltage with power engineering frequency (line frequency)
9.2 Electromagnetic compatibility
2.0 GHz to 6 GHz
3 V/m
Corresponds to degree of severity
Corresponds to degree of severity
Corresponds to degree of severity
Technical specifications
Corresponds
to degree of
severity
3
3
5
5
3
3
139