Maintenance

8.10 Firmware update for the server module

8.10
Firmware update for the server module
By default, the server module of the ET 200SP HA is not configured in HW Config.
Consequently, you cannot select the module in HW Config.
This section describes the steps required to update the firmware of the server module.
Requirements
● A connection to the IO device (ET 200SP HA Station) is possible.
● The storage location of the file for the firmware update is known.
Procedure
1. Open SIMATIC Manager.
2. Select the menu command PLC > Show accessible devices.
3. Select the station.
4. Select the menu command PLC > Update Firmware".
The "Update Firmware" dialog opens.
5. Select the "Change slot" button.
6. Enter the slot of the server module in the "Change slot" dialog.
7. Select the "Browse" button in the "Firmware File" area.
8. Navigate to the firmware file and select it.
9. Check the suitability of the selected file for the firmware update in the "Firmware File" area.
10.Select the "Activate firmware after update" check box.
11.Click the "Execute" button.
See also
Technical specifications for the modules (Page 148)
132
ET 200SP HA Distributed I/O system
System Manual, 08/2019, A5E39261167-AD