Siemens SIMATIC ET 200SP HA System Manual page 140

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Technical specifications
9.2 Electromagnetic compatibility
Table 9-7
Inspection according to IEC 61000-4-16
and IEC 61000-4-18
● 10 V - 1 V (15 Hz - 150 Hz)
● 1 V (150 Hz - 1.5 kHz)
● 1 V - 10 V (1.5 kHz - 15 kHz)
● 10 V (15kHz - 150 kHz)
See the table "Conditions for the design of field wiring".
Table 9-8
Inspection according to IEC 61000-4-16
and IEC 61000-4-18
Signals:
● 1.0 kV (common mode, 1 MHz)
● 0.5 kV (differential mode, 1 MHz)
DC supply:
● 1.0 kV (common mode, 1 MHz)
● 0.5 kV (differential mode, 1 MHz)
● 0.5 kV (common mode, 10 MHz)
See the table "Conditions for the design of field wiring".
Conditions for the design of field wiring
To fulfill these requirements, the field wiring for the modules should be performed as stipulated
in the following table.
Module
AI 16xI 2-wire HART HA
AI16xTC/8xRTD 2-/3-/4-wire HA
AI-DI16/DQ16x24VDC HART HA
AQ 8xI HART HA
DI 16x24VDC HA
DI 8x230VAC HA
DI 8x24..125VDC HA
DI 16xNAMUR HA
DI 32x24VDC HA
DQ 16x24VDC/0,5A HA
DQ 32x24VDC/0.5A HA
AI16xTC/8xRTD 2-/3-/4-wire HA
AI-DI16/DQ16x24VDC HART HA
140
Asymmetrical conducted interference
Damped oscillatory waves
Corresponds to degree of severity
Corresponds to degree of severity
Article number
6DL1134-6TH00-0PH1
6DL1134-6JH00-0PH1
6DL1133-6EW00-0PH1
6DL1135-6TF00-0PH1
6DL1131-6BH00-0PH1
6DL1131-6GF00-0PK0
6DL1131-6DF00-0PK0
6DL1131-6TH00-0PH1
6DL1131-6BL00-0PH1
6DL1132-6BH00-0PH1
6DL1132-6BL00-0PH1
6DL1134-6JH00-0EH1
6DL1133-6EW00-0EH1
System Manual, 08/2019, A5E39261167-AD
3
2
2
Design of the field wiring
Shielded
Shielded
Shielded
Shielded
Unshielded
Unshielded
Unshielded
Shielded
Unshielded
Unshielded
Unshielded
Shielded
Shielded