Siemens SIMATIC ET 200SP HA Equipment Manual
Hide thumbs Also See for SIMATIC ET 200SP HA:

Advertisement

Quick Links

SIMATIC
ET 200SP HA
DQ 32x24VDC/0.5A HA
Equipment Manual
6DL1132-6BL00-0PH1
08/2019
A5E48262762-AB
Security information
Preface
2D Matrix code (QR code /
EAN code)
Product overview
Connection
Parameters
Displays and interrupts
Technical specifications
Drivers, parameters,
diagnostics messages and
address space
1
2
3
4
5
6
7
8
A

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC ET 200SP HA

  • Page 1 Security information Preface 2D Matrix code (QR code / EAN code) SIMATIC Product overview ET 200SP HA DQ 32x24VDC/0.5A HA Connection Parameters Equipment Manual Displays and interrupts Technical specifications Drivers, parameters, diagnostics messages and address space 6DL1132-6BL00-0PH1 08/2019 A5E48262762-AB...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Security information..........................5 Preface ..............................7 2D Matrix code (QR code / EAN code) ....................9 Product overview ..........................11 I/O module......................... 11 Accessories ........................12 Output disable switch ......................13 Pulling the I/O module in runtime..................13 Terminal blocks........................
  • Page 4 Table of contents Technical specifications ........................27 Drivers, parameters, diagnostics messages and address space ............31 Parameter assignment ....................... 31 Parameter assignment and structure of the module/channel parameters......32 Diagnostic messages......................34 Maintenance events......................35 Address space ........................35 Tables Table A-1 Address space of the DQ 32x24VDC/0.5A HA ................
  • Page 5: Security Information

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber...
  • Page 6 Security information DQ 32x24VDC/0.5A HA Equipment Manual, 08/2019, A5E48262762-AB...
  • Page 7: Preface

    Preface Validity of the documentation This manual describes the following I/O module: System family I/O module Article No. SIMATIC; DQ 32x24VDC/0.5A HA 6DL1132-6BL00-0PH1 Distributed I/O System; ET 200SP HA It supplements the ET 200SP HA Distributed I/O system system manual. Functions that generally relate to the system are described in this manual.
  • Page 8 Preface DQ 32x24VDC/0.5A HA Equipment Manual, 08/2019, A5E48262762-AB...
  • Page 9: Matrix Code (Qr Code / Ean Code)

    The 2D matrix code on the product is a coded representation of the product-specific article number. Access to product-related information For reading the 2D matrix code, SIEMENS offers an app for mobile use. Information about the app and the download can be found on the Internet: "Mobile use via app (https://support.industry.siemens.com/cs/ww/en/sc/2067)".
  • Page 10 2D Matrix code (QR code / EAN code) DQ 32x24VDC/0.5A HA Equipment Manual, 08/2019, A5E48262762-AB...
  • Page 11: Product Overview

    Product overview I/O module Definition The DQ 32x24VDC/0.5A I/O module is a digital output module with 32 power outputs for process control. In addition to the technical specifications, this module has the following properties: • Source output (PNP, switching to P potential) •...
  • Page 12: Accessories

    Product overview 4.2 Accessories Description The I/O module consists of the following components: 32 x2 4V DC /0 ,5 DI AG M T 1 DQ .0 + DQ .1+ 3 DQ .2+ DQ .3 + 5 DQ .4 + DQ .5 + 7 DQ .6 + DQ .7+ 9 DQ .0 +...
  • Page 13: Output Disable Switch

    Product overview 4.4 Pulling the I/O module in runtime • Reference identification label • Shield connector Output disable switch Definition The output disable switch switches the I/O module load-free. NOTICE Dangerous plant conditions possible (disconnect the load) If you want to pull the I/O module in runtime, you have to press the output disable switch for 3 seconds for the I/O module to be load free (deenergized).
  • Page 14: Terminal Blocks

    Product overview 4.5 Terminal blocks Terminal blocks Definition The terminal blocks provide the process terminals (push-in terminals) for the connection of components, such as devices. Description The following terminal blocks are available for the I/O module: Article No. Color Description 6DL1193-6TP00-0DH1 6DL1193-6TP00-0BH1 Dark...
  • Page 15: Connection

    Connection Pin assignment Definition The pin assignment provides information about the arrangement and identification of the terminals when wiring a connector. Description The general pin assignment is structured as follows: Terminal Allocation Terminal Allocation Explanations DQ a/DQ.0+ DQ a/DQ.1+ DQ a /DQ.n+: Output signal, channel n (0…7) DQ b /DQ.n+: Output signal, channel n (8…15) DQ a/DQ.2+ DQ a/DQ.3+...
  • Page 16: Sample Connection Scheme For 1-Wire Connection

    Connection 5.3 Wiring diagram for actuators General pin assignment with potential distributor The potential distributor with 36 M terminals is located on the right side of the terminal block. The left side corresponds to the general pin assignment. Note Connection information •...
  • Page 17: Schematic Circuit Diagram

    Connection 5.4 Schematic circuit diagram Schematic circuit diagram Definition A block diagram contains the schematic representation of individual function blocks. Description The block diagram for the I/O module is structured as follows: DQ 32x24VDC/0.5A HA Equipment Manual, 08/2019, A5E48262762-AB...
  • Page 18 Connection 5.4 Schematic circuit diagram DQ 32x24VDC/0.5A HA Equipment Manual, 08/2019, A5E48262762-AB...
  • Page 19: Parameters

    Parameters Parameter types Definition You define and thereby influence the functions supported by the module operation of the I/O module via the parameter types. Module/channel parameters Definition Module/channel parameters are specific parameters whose configuration can affect the entire module or channels. Note Each re-parameterization resets the corresponding reaction.
  • Page 20: Explanation Of The Module/Channel Parameters

    Parameters 6.3 Explanation of the module/channel parameters Parameters Value range Default Parameter re‐ Efficiency range assignment in Potential group (Page 21) Use potential Module • Potential group of the left mod‐ group of the left ule (dark gray terminal block) module •...
  • Page 21: Channel Activated

    Parameters 6.3 Explanation of the module/channel parameters 6.3.3 Channel activated Definition Specifies whether a channel is activated or deactivated. 6.3.4 Reaction to CPU STOP Definition Specifies the behavior of the digital output as a reaction to CPU stop or to failure of communication between the interface module and CPU.
  • Page 22: Double-Width Terminal Block

    Parameters 6.3 Explanation of the module/channel parameters The potential group also ends if there is a black terminal block next to it. Black terminal blocks are fed individually and cannot be included in potential groups. You can find additional information on the configuration of the potential group in the system manual SIMATIC;...
  • Page 23: Displays And Interrupts

    Displays and interrupts Status and error displays Definition The LED displays are status and fault indicators. Diagnostic messages and maintenance events, as well as their possible causes and solutions, are described in the diagnostic messages and maintenance events. Diagnostic messages (Page 34) Description The following figure explains the LED displays of the I/O module.
  • Page 24: Leds

    Displays and interrupts 7.2 LEDs LEDs 7.2.1 DIAG LED Definition The DIAG LED provides you diagnostic information. Description The diagnostic display of the DIAG LED is as follows: DIAG LED Meaning The power supply of the ET 200SP HA is disrupted or switched off. Module is not configured.
  • Page 25: Channel Status Led

    Displays and interrupts 7.3 Interrupts 7.2.3 Channel status LED Definition The green LED channel status shows the signal level at the input terminal. Description The channel status LED indicates the following statuses: LED channel status Meaning • Process signal = 0 or channel disabled •...
  • Page 26 Displays and interrupts 7.3 Interrupts Description The I/O module generates a diagnostics interrupt at the following events: • Supply voltage L+ missing • Parameter assignment error • Channel/component temporarily unavailable • Short-circuit to ground • Retentive memory in carrier module defective •...
  • Page 27: Technical Specifications

    Technical specifications Technical specifications of the DQ 32×24VDC/0.5A HA Article number 6DL1132-6BL00-0PH1 General information Product type designation DQ 32x24VDC/0.5A HA Firmware version V1.0 • FW update possible Usable terminal block TB type H1 and N0 Color code for module-specific color identifica‐ CC00 tion plate Product function...
  • Page 28 Technical specifications Article number 6DL1132-6BL00-0PH1 Power loss, typ. 1.6 W; minimum - typ. specification not possible because load-dependent Address area Address space per module 4 byte; QI of the outputs • Inputs 4 byte • Outputs Digital outputs Number of digital outputs Current-sinking Current-sourcing Digital outputs, parameterizable...
  • Page 29 Technical specifications Article number 6DL1132-6BL00-0PH1 10 A – up to 60 °C, max. Cable length 1 000 m • shielded, max. 600 m • unshielded, max. Interrupts/diagnostics/status information Diagnostics function Substitute values connectable Alarms • Diagnostic alarm Diagnoses • Monitoring the supply voltage –...
  • Page 30 Technical specifications Power supply (SELV/PELV) Ensure that the power supply is safely disconnected in accordance with the following standard: IEC/UL61010-2-201 This separation is referred to in the standard as SELV (Safety Extra Low Voltage) / PELV (Protective Extra Low Voltage). Make sure that the supply and input voltages of the ET 200SP HA IO device are generated safely separately: Nominal value: 24 VDC +-20% (...
  • Page 31: Drivers, Parameters, Diagnostics Messages And Address Space

    Drivers, parameters, diagnostics messages and address space Parameter assignment Parameter assignment in the user program You can reconfigure individual channels of the module in RUN without this having an effect on the other channels. Changing parameters in RUN The parameters are transferred to the module with the "WRREC" instruction via data record 128. Output parameter STATUS of the WRREC If errors occur when transferring parameters with the "WRREC"...
  • Page 32: Parameter Assignment And Structure Of The Module/Channel Parameters

    Drivers, parameters, diagnostics messages and address space A.2 Parameter assignment and structure of the module/channel parameters Parameter assignment and structure of the module/channel parameters Structure of data record 128 Data record 128 has a length of 76 bytes. It contains the channel parameters of the 32 channels. Figure A-1 Structure of data record 128 DQ 32x24VDC/0.5A HA...
  • Page 33: Figure A-2 Header Information And Module Parameters Of Data Record 128

    Drivers, parameters, diagnostics messages and address space A.2 Parameter assignment and structure of the module/channel parameters Header information and module parameters The following figure shows the configuration of the header information and module parameters. Figure A-2 Header information and module parameters of data record 128 Channel parameters Each channel parameter block contains the channel parameters for a digital output (2 bytes).
  • Page 34: Diagnostic Messages

    Drivers, parameters, diagnostics messages and address space A.3 Diagnostic messages The following figure shows the configuration of the channel parameters for channels 0 to 31. x = 12 + (channel number * 2); with channel number = 0…31 All unused bits and the bits or bytes marked as "reserved" must be set to zero. You activate a channel parameter by setting the corresponding bit to "1"...
  • Page 35: Maintenance Events

    Drivers, parameters, diagnostics messages and address space A.5 Address space Diagnostics Error code Assign‐ Meaning Remedy message ment Channel/compo‐ Module Firmware update is in progress or has been • Restart the firmware update nent temporarily canceled during the update. The module gen‐ •...
  • Page 36: Table

    Drivers, parameters, diagnostics messages and address space A.5 Address space Address space The following figure shows the mapping of the address space of the DQ 32x24VDC/0.5A HA: Table A-1 Address space of the DQ 32x24VDC/0.5A HA IB x + AB x + QDQ7 QDQ6 QDQ5...