Toshiba 1400SE Series Operation Manual

Single phase - .6/.8/1.0/1.2/1.5/2.0/2.4 kva, single phase - .6/.8/1.0/1.5 kva plus
Table of Contents

Advertisement

TOSHIBA
UNINTERRUPTIBLE POWER SYSTEM
SINGLE PHASE - .6/.8/1.0/1.2/1.5/2.0/2.4 kVA
SINGLE PHASE - .6/.8/1.0/1.5 kVA PLUS
and
including
MANUFACTURED IN THE U.S.A.
OPERATION MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba 1400SE Series

  • Page 1 TOSHIBA UNINTERRUPTIBLE POWER SYSTEM SINGLE PHASE - .6/.8/1.0/1.2/1.5/2.0/2.4 kVA SINGLE PHASE - .6/.8/1.0/1.5 kVA PLUS including MANUFACTURED IN THE U.S.A. OPERATION MANUAL...
  • Page 2 TOSHIBA...
  • Page 3 TOSHIBA NOTE Any electrical or mechanical modifications to this equipment, without prior written consent of Toshiba International Corporation, will void all warranties and may void UL listing and/or CSA certification. Unauthorized modifications also can result in personal injury, death, or destruction of the equipment.
  • Page 4: Table Of Contents

    TOSHIBA CONTENTS SECTION PAGE Disclaimer ....................i Contents ....................ii-iii Introduction ....................iv General Safety Instructions ..............v Important Safety Instructions ............... vi-vii Product Description ................1-1 Theory of Operation ................1-1 Application and Use ................1-1 Power Backup................. 1-1 Power Conditioning .................1-1 Inspection/Storage/Disposal ..............
  • Page 5: Contents

    TOSHIBA CONTENTS (Cont'd) SECTION PAGE Operating the UPS (cont'd) ..............5-1 Operation Monitoring ..............5-5 5.3.1 Visual Indicator Functions ............5-5 5.3.2 Audible Alarm Functions ............5-5 5.3.3 Visual and Audible Indicator Function Chart ......5-5 Front Panel Layout .................5-6 UPS Run Mode Display ..............5-6 Battery Recharging .................5-7...
  • Page 6: Introduction

    TOSHIBA INTRODUCTION safely Read this operation manual All safety warnings must be followed Follow all precautions General safety instructions are found on page v and important safety instructions are found on pages vi and vii. Read and save these instructions...
  • Page 7: General Safety Instructions

    TOSHIBA GENERAL SAFETY INSTRUCTIONS Warnings Danger WILL DANGER Warning COULD COULD WARNING Caution CAUTION Attention warnings ATTENTION Danger Caution Electrical warnings Explosion warnings...
  • Page 8: Important Safety Instructions

    TOSHIBA IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS- Model Capacity Manufacturer Type Quantity (except UC1A1A020C6RKB) CAUTION CAUTION CAUTION WARNING WARNING...
  • Page 9 TOSHIBA IMPORTANT SAFETY INSTRUCTIONS WARNING Proper maintenance to the battery system of this unit must be done by a WARNING qualified service technician, this is essential to the safety and reliability of your UPS system. Refer to service manual. A battery can present a risk of electrical shock and high short DANGER circuit current.
  • Page 10 TOSHIBA INSTRUCTIONS IMPORTANTES CONCERNANT SÉCURITÉ CONSERVER CES INSTRUCTIONS ATTENTION ATTENTION Model Capacity Manufacturer Type Quantity (except UC1A1A020C6RKB) ATTENTION viii...
  • Page 11: Product Description

    TOSHIBA Product Description Theory of Operation Application and Use Power Backup Power Conditioning 1 - 1...
  • Page 12: Inspection/Storage/Disposal

    TOSHIBA Inspection/Storage/Disposal Inspection of the new UPS equipment After Uncrating: Storage of UPS equipment. Avoid: Before storing: Storing: ° ° ° ° ° ° After storing: ° ° ° ° ° ° ° ° ° ° Disposal It is illegal to dump lead-acid batteries in landfills or to dispose of them improperly.
  • Page 13: Precautions

    TOSHIBA Precautions CAUTION Installation Precautions (General) CAUTION Installation Precautions (Rack mounted) secured 3 - 1...
  • Page 14: Prestart Precautions

    TOSHIBA Precautions CAUTION Prestart Precautions CAUTION Operating Precautions The UPS may be supplying power to the output load receptacles through the bypass circuit. 3 - 2...
  • Page 15: Specifications

    DB9 female connector (Pin 9 not used) Options Software for unattended computer shutdown Contact Toshiba for details on this option External battery pack Contact Toshiba for details on this option (*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
  • Page 16 DB9 female connector (Pin 9 not used) Options Software for unattended computer shutdown Contact Toshiba for details on this option External battery pack Contact Toshiba for details on this option (*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
  • Page 17 DB9 female connector (Pin 9 not used) Options Software for unattended computer shutdown Contact Toshiba for details on this option External battery pack Contact Toshiba for details on this option (*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
  • Page 18: Plus Series Specifications (W/Output Isolation Transformer)

    DB9 female connector (Pin 9 not used) Options Software for unattended computer shutdown Contact Toshiba for details on this option External battery pack Contact Toshiba for details on this option (*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
  • Page 19 DB9 female connector (Pin 9 not used) Options Software for unattended computer shutdown Contact Toshiba for details on this option External battery pack Contact Toshiba for details on this option (*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
  • Page 20: Standard Series Specifications (Rack Mounted)

    DB9 female connector (Pin 9 not used) Options Software for unattended computer shutdown Contact Toshiba for details on this option External battery pack Contact Toshiba for details on this option (*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
  • Page 21: Operating The Ups

    TOSHIBA Operating the UPS Operation Modes 5.1.1 AC Input Mode (normal operation) = power flow Power flow in AC input mode for 600, 800, 1000, and 1200 VA Models Fuse L5-30P for (2400VA) Power flow in AC input mode for 1500, 2000, and 2400 VA Models...
  • Page 22: Battery Backup Mode

    TOSHIBA Operating the UPS Operation Modes (Cont'd) 5.1.2 Battery Backup Mode Power flow in battery backup mode for 600, 800, 1000, and 1200 VA Models Fuse L5-30P for (2400VA) Power flow in battery backup mode for 1500, 2000, and 2400 VA Models...
  • Page 23: Circuit Bypass Mode

    TOSHIBA Operating the UPS Operation Modes (Cont'd) 5.1.3 Circuit-bypass Mode Power flow in circuit-bypass mode for 600, 800, 1000, and 1200 VA Models L5-30P for (2400VA) Power flow in circuit-bypass mode for 1500, 2000, and 2400 VA Models The energy flow must be transferred manually from the UPS's bypass circuit back to the inverter circuit after first correcting the fault.
  • Page 24: System Protection Features

    TOSHIBA Operating the UPS System Protection Features Input Overcurrent Bypass Abnormal OUTPUT XFMR (Plus Series) FUSE Rectifier/ Output Input Inverter charger/ chopper Batteries Output Overvoltage/ Low Battery Undervoltage Current Limit Level Overheating Power flow Overload Input Overcurrent Bypass Abnormal OUTPUT XFMR...
  • Page 25: Operation Monitoring

    TOSHIBA Operating the UPS Operation Monitoring 5.3.1 Visual Indicator Functions AC LINE NVERTER FAULT 5.3.2 Audible Alarm Functions 5.3.3 Visual and Audible Indicator Function Chart Audible Condition Cause Visual Alarm Indicators Operation Pattern 1.5s .5s .5s 5 - 5...
  • Page 26: Front Panel Layout

    TOSHIBA Operating the UPS Front Panel Layout green green UPS Inverter Mode Display green UPS Run Mode Display Chart green green Remove overload as quickly as possible to prevent fault (fault timeouts vary depending on overload condition). green = Steady-lit LED...
  • Page 27: Battery Recharging

    TOSHIBA Operating the UPS (Cont'd) Battery Recharging Rated battery voltages 5 - 7...
  • Page 28: Battery Backup Time

    TOSHIBA Operating the UPS Battery Backup Time Battery Low Voltage Tolerances UPS Capacity 1000 1200 1500* 2000** 2400 600+ 800+ 1000+ 1500+ in VA Battery Check Function If the batteries are indicated "bad" then STOP the UPS and allow a 24 hour charge on the batteries before restarting.
  • Page 29: Ups Control Interface

    TOSHIBA UPS Control Interface Remote Contact and IBM AS/400 DB9 Male Connector Outline (NO) (NO) (NO) (NO) (NC) (NO) Notes: inactive states 6 - 1...
  • Page 30: Rs-232C Communication Interface

    TOSHIBA UPS Control Interface RS-232C Communication Interface Output voltage Output current Battery voltage Input frequency Output frequency Utility power OK Low battery voltage detected UPS in BYPASS mode UPS in NORMAL mode Input and output frequency synchronized UPS ‘fault’ occurred...
  • Page 31: Troubleshooting Procedures

    TOSHIBA Troubleshooting Procedures Non-Fatal Fault Mode Non-Fatal Fault Mode Display Chart OUTPUT BATTERY OUTPUT BATTERY OUTPUT BATTERY OUTPUT BATTERY ately OUTPUT BATTERY 7 - 1...
  • Page 32: Fatal Fault Mode

    TOSHIBA Troubleshooting Procedures Fatal Fault Mode Fatal Fault Mode Display Chart OUTPUT BATTERY OUTPUT BATTERY OUTPUT BATTERY OUTPUT BATTERY 7 - 2...
  • Page 33: Preventive Maintenance/Parts Replacement

    TOSHIBA Preventive and Scheduled Maintenance/Parts Replacement Preventive Maintenance Before performing any maintenance the technician should CAUTION be familiar with and follow the important safety instructions located on pages vi and vii. Proper maintenance of the battery system of this unit by a...
  • Page 34: Input/Output Fuse Rating Chart

    TOSHIBA Preventive and Scheduled Maintenance/Parts Replacement Input/Output Fuse Rating Chart Fuse rating 8 - 2...
  • Page 35: External Dimensions/Shipping Weights/Panel Layout

    TOSHIBA External Dimensions/Shipping Weights/Panel Layout External Dimensions for 600 through 1200 VA Models 9 - 1...
  • Page 36: External Dimensions For 1500 Through 2400 Va Model

    TOSHIBA External Dimensions/Shipping Weights/Panel Layout External Dimensions for 1500 through 2400 VA Models 9 - 2...
  • Page 37 TOSHIBA External Dimensions/Panel Layout/Shipping Weights External Dimensions for 1500 and 2000 VA Model (Rack Mounted) Side View 9 - 3...
  • Page 38: Remote Run/Stop

    TOSHIBA External Dimensions/Panel Layout/Shipping Weights Remote Run/Stop CAUTION: ATTENTION: 9 - 4...
  • Page 39: Panel Layout

    TOSHIBA External Dimensions/Panel Layout/Shipping Weights Panel Layout Panel Layout (Rack mounted) OUTPUT STOP INVERTER BATTERY AC LINE FAULT ON-LINE UPS Shipping Weights Shipping Weight Model Pounds Kilograms 600 VA 27.2 800 VA 29.9 1000 VA 31.8 1200 VA 34.5 1500 VA 43.6...
  • Page 40 TOSHIBA...
  • Page 41 TOSHIBA TOSHIBA INTERNATIONAL CORPORATION INDUSTRIAL DIVISION 13131 West Little York Rd., Houston Texas 77041 Tel: [800] 231-1412 Fax: [713] 466-8773 Telex: 762078 Printed in U.S.A.