Understanding UPS Operation

Figure 51. Path of Current Through the UPS in Normal Mode

Bypass Input
Rectifier Input
5 5 . . 2 2 . . 4 4 B B y y p p a a s s s s M M o o d d e e
The critical load is not protected from voltage or frequency fluctuations or power outages while the UPS is in
Bypass mode.
The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure (if
configured for capacity). If configured for redundancy (N+1) the UPS would remain on line in Normal mode if
one UPM failed. The UPS can also be transferred from Normal mode to Bypass mode manually. The bypass
source supplies the commercial AC power to the load directly.
through the UPS system when operating in Bypass mode.
In Bypass mode, the output of the system is provided with three-phase AC power directly from the system
input. While in this mode, the output of the system is not protected from voltage or frequency fluctuations or
power outages from the source. Some power line filtering and spike protection is provided to the load but no
active power conditioning or battery support is available to the output of the system in the Bypass mode of
operation.
The internal bypass is comprised of a solid-state, silicon-controlled rectifier (SCR) continuous static switch. The
static switch is used instantaneously anytime the inverter is unable to support the applied load. The continuous
static switch is wired in parallel with the rectifier and inverter.
The static switch, being an electronically-controlled device, can be turned on immediately to pick up the load
from the inverter while the inverter switchgear opens to isolate the inverter.
If the UPS transfers to Bypass mode from Normal mode due to any reason other than operator intervention,
the UPS automatically attempts to transfer back to Normal mode (up to three times within a ten minute period).
The fourth transfer locks the critical load to the bypass source and requires operator intervention to transfer.
104
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
Rectifier
Rectifier
Switchgear
Switchgear
Closed
Open
Static
Switch
Inverter
Battery
Converter
Battery
Switchgear
Battery
CAUTION
Figure 52
Output
Inverter
Switchgear
Main Power Flow
Trickle Current
Energized
De-Energized
shows the path of electrical power