Section 5 BUFFER MEMORY
5.5.4
1-2 voltage waveform data 1 to 300 (Un\G10004 - Un\G10603),
2-3 voltage waveform data 1 to 300 (Un\G12004 - Un\G12603)
Waveform data of each inter-wire voltage is stored.
Stores data of the number of the waveform data of voltage (Un\G10001) from waveform data 1.
(1)
Details of stored data
(a) Storage format
Data is stored as double-word 32-bit signed binary in the buffer memory.
・Data range: -999999999 to 99999999 (-999999.999 to 99999.999 V)
(b) Storage range
The range differs according to the period of measured data acquisition clock.
Refer to "" as to details.
(c) Unit
V *Unit is fixed.
-3
×10
(d) Update timing
It will be updated every measuring cycle. For measuring cycle, refer to "5.2.12".
5.5.5
Multiplying factor of current waveform data (Un\G16000)
The multiplying factor of waveform data of current is stored.
(1)
Details of stored data
(a) Storage format
Data is stored as 16-bit signed binary in the buffer memory.
・Data range: -3 (fixed)
(b) Update timing
Because it is fixed at -3, there is no update.
5.5.6
Number of the waveform data of current (Un\G16001)
The number of the waveform data during a period of measured data acquisition clock is stored.
(1)
Details of stored data
(a) Storage format
Data is stored as 16-bit signed binary in the buffer memory.
・Data range: 0 to 300
(b) Update timing
It will be updated every measuring cycle. For measuring cycle, refer to "5.2.12".
95
RE81WH