Mitsubishi Electric MELSEC iQ-R Series User Manual page 86

Energy measuring module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Section 5 BUFFER MEMORY
(1)
Details of stored data
(a) Storage format
As indicated below, Data is stored as BCD code in the buffer memory.
Buffer memory address
Un\G722
/Un\G730
Un\G723
/Un\G731
Un\G724
/Un\G732
Un\G725
/Un\G733
Un\G726
/Un\G734
(b) Update timing
It will be updated every measuring cycle if it exceeds the power factor max. value or goes under the power
factor min. value.
For measuring cycle, refer to "5.2.12".
b15
b12 b11
b8 b7
Year
b15
b12 b11
b8 b7
Month
b15
b12 b11
b8 b7
Hour
Minute
b15
b12 b11
b8 b7
Second
0 fixed
b15
b12 b11
b8 b7
0 fixed
Millisecond
85
Storage format
b4 b3
b0
e.g.) Year 2010
2010h
b4 b3
b0
e.g.) July 30
0730h
Day
b4 b3
b0
e.g.) 10:35
1035h
b4 b3
b0
e.g.) 48 sec Friday
4805h
Day of the week
0
Sunday
1
Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
b4 b3
b0
e.g.) 172 millisecond
172h
RE81WH

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Melsec re81wh

Table of Contents