Section 6 SETTING AND PROCEDURE FOR OPERATION
■ When wiring single-phase 2-wire circuit
5A current sensor is not used L3. As shown below, L3 remove connector, and connector with insulating tape.
■ Extending the cable of 5 A current sensor
If the cable from current sensor is too short, you can extend it by using an extension cable as shown below.
Extension cable (standard)
Model name
EMU2-CB-T1M
Cable length
Extension cable (separate)
Model name
EMU2-CB-T1MS
Cable length
Follow the procedure below to extend for cable of EMU2-CT5.
(1)
Connecting 5 A current sensor and extension cable (standard)
EMU2-CT5 (0.5m)
L1
L3
EMU2-CB-T5M
1 m
5 m
EMU2-CB-T5MS
1m
Insulating tape
EMU2-CT5
EMU2-CB-T10M
10 m
EMU2-CB-T10MS
5m
10m
EMU2-CB-T**M (1 to 10m)
110
RE81WH
EMU2-CB-Q5A (0.5m)