Section 6 SETTING AND PROCEDURE FOR OPERATION
6.3.2
How to connect wires
(1)
Follow the "6.3.3 How to wire" for external connection to RE81WH.
(2)
Use applicable wire as described below.
At the connection between the secondary terminal of the dedicated current sensor (excludes EMU2-CT5)
and current input terminals, use twisted pair cable.
Applicable wire
(Usable electric wire)
(3)
Stripping length of the used wire in use has to be 10 to 11mm. Check the stripping length using the gauge
of RE81WH main module.
(4)
When stranded wire is used, a bar terminal must be used.
Recommended bar terminal
(5)
When inserting and detaching cables to/from the terminal, use the push button. Check that the wire is
securely inserted.
(6)
Insert a wire to the terminal all the way until it touches the end.
Single wire: AWG24 - AWG16 (φ0.52 - 1.29mm)
Stranded wire: AWG20 - AWG16 (0.52 - 1.30mm
Stripping length of the wire
10 to 11mm
TGV TC-1.25-11T (Made by Nichifu) or equivalent
102
RE81WH
)
2