Mitsubishi Electric MELSEC iQ-R Series User Manual page 36

Energy measuring module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Section 3 NAME AND FUNCTION OF EACH PART
3.4.6
Integrated value set function
This is a function that can set the integrated value (electric energy (consumption, regeneration), reactive
energy (consumption lag)) to an arbitrary value.
It is used to clear integrated value.
(1)
Setting procedure
Setting procedures are as follows.
(a) Set the integrated value setting target (Un\G51) in the buffer memory.
Setting range is as follows.
Setting value
0
1
2
3
(b) Set the integrated value setting value (Un\G52, 53) in the buffer memory.
・Configurable range: 0 to 999999999
・The unit used for the setting value is the same as that used for the electric energy and reactive
energy output to the buffer memory.
For details, refer to "5.3.2".
(c) Turn Integrated value set request (YnC) from OFF to ON to enable the setting.
Integrated value set completion flag (XnC) turns ON after Integrated value set request (YnC) is set OFF
to ON.
(d) After checking that integrated value set completion flag (XnC) turns ON and setting is completed, set
the integrated value set request (YnC) to OFF.
After detected that the integrated value set request (YnC) turns OFF, the integrated value set completion
flag (XnC) turns OFF.
Integrated value set request (YnC)
Integrated value set completion flag (XnC)
積算値セット完了フラグ(X3)
(2)
Default value
Integrated value setting target (Un\G51) is set to 0 (No set).
Integrated value setting value (Un\G52, 53) is set to 0.
Description
No set
Electric energy (consumption)
Electric energy (regeneration)
Reactive energy (consumption lag)
積算値セット要求(Y3)
OFF
OFF
Figure 3.4.6 Integrated value setting procedure
ON
OFF
ON
OFF
35
RE81WH

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Melsec re81wh

Table of Contents