Setting The Limit Values - ProMinent delta Operating Instructions Manual

Control module
Table of Contents

Advertisement

6.6

Setting the limit values

Main
Operation
proControl
Set
Clear
Controller
Setpoint
Parameter
Basic load
Limit value
Fig. 12: Setting the limit values
Sensor
top
Chlorine
0 ppm
pH
0 pH
Redox
0 mV
You have the possibility of setting the permissible value for the
controlling for each sensor type. When a measurement value lies
outside this limit value, the control will be discontinued. Basic load
control is only active in this case.
If the measurement value lies outside the limit value than a
warning is reported and the symbol
display of the delta
Set
Sensor calibr.
Controller
Concentration
Aux.
Chlorine sensor
Limit value
high: 10.0 ppm
low: 0.0 ppm
or
pH sensor
Limit value
high: 12.0 pH
low: 3.0 pH
or
Redox sensor
Limit value
high: 700 mV
low: 200 mV
Factory setting
Settings
bottom
20 ppm
0 ppm up to the maximum value of the sensor. In incre‐
ments of 0.1 ppm
14 pH
0 pH to 14 pH. In increments of 0.1 pH
1,000 mV
0 mV to 1,000 mV. In increments of 1 mV
Operating Schematics / Display Symbols
Hysteresis
An hysteresis is installed here so that when in the
range of the limit value of the control module delta
switching is not constantly carried out between the
control and base load metering.
The hysteresis is approx. 2% of the measuring range:
(„Limit value up" minus „Limit value down") * 2 %
®
solenoid metering pump.
Chlorine sensor
Limit value
high: [10.0] ppm
low: 0.0 ppm
or
pH sensor
Limit value
high: [12.0] pH
low: 3.0 pH
or
Redox sensor
Limit value
high: [700] mV
low: 200 mV
is displayed in the status
!
,
®
A0313
27