Technical Data - Samson 43-3 Mounting And Operating Instructions

Table of Contents

Advertisement

3.2 Technical data

The regulator nameplate provides informa-
tion on the regulator version (see the 'Mark-
ings on the device' section).
Note
More information is available in Data Sheet
u T 2173.
Process medium and scope of application
Designed for mixing or diverting service in
heating or cooling installations The Type 43-
3 Temperature Regulator is designed to
maintain the temperature at the control ther-
mostat sensor to the adjusted set point.
− Medium: water
− Max. temperature up to 150 °C
− Temperature set points from 0 to 150 °C
− Valve sizes G ½ to 1 · DN 15 to 50
− PN 25
Testing according to DIN EN 14597
The Type 43-3 Temperature Regula-
tor combined with the Type 2439
Safety Temperature Limiter or the
Type 2403 Safety Temperature Moni-
tor is tested according to DIN. The
registration number is available on
request.
EB 2173 EN
Design and principle of operation
EC type examination
The DVGW type examination certificate is
included in the 'Certificates' section.
Noise emissions
SAMSON is unable to make general state-
ments about noise emissions. The noise emis-
sions depend on the regulator version, plant
facilities, process medium and operating
conditions.
Temperature range
Depending on how the Type 43-3 Regulator
is configured, it can be used up to max.
150 °C. The minimum temperature is limited
by the seal material used in the regulator
(see Table 3-1).
Dimensions and weights
Table 3-3 provides a summary of the dimen-
sions and weights. The lengths and heights
in the dimensional drawings are shown on
page 3-8.
3-5