hilscher NIOT-E-TPI51-EN-RE User Manual

hilscher NIOT-E-TPI51-EN-RE User Manual

Netiot edge gateway
Hide thumbs Also See for NIOT-E-TPI51-EN-RE:
Table of Contents

Advertisement

Quick Links

User manual
netIOT Edge Gateway
NIOT-E-TPI51-EN-RE (Connect)
V1.2.0.0
Hilscher Gesellschaft für Systemautomation mbH
www.hilscher.com
DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NIOT-E-TPI51-EN-RE and is the answer not in the manual?

Questions and answers

Summary of Contents for hilscher NIOT-E-TPI51-EN-RE

  • Page 1 User manual netIOT Edge Gateway NIOT-E-TPI51-EN-RE (Connect) V1.2.0.0 Hilscher Gesellschaft für Systemautomation mbH www.hilscher.com DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 2: Table Of Contents

    8.3.4 Setting the system time...................  42 8.3.5 Configure ports for HTTP/HTTPS communication..........  44 8.3.6 Backup and restore.................. 46 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 3 10.2 Example 2: MQTT input node .................. 136 10.3 Example 3: MQTT output node .................. 140 10.4 Example 4: Fieldbus input node................... 144 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 4 The configuration of IP address area............ 211 14.3.2 Selecting the protocols to scan for field devices ...........  214 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 5 Working with certificates for client authentication .........  269 16.6.3 Working with key files for client authentication .......... 272 17 Technical data ........................ 275 17.1 Technical data NIOT-E-TPI51-EN-RE ................. 275 17.2 Technical data PROFINET IO Device................ 277 17.3 Technical data EtherNet/IP Adapter................ 278 18 Approvals .......................... 279 18.1 Federal Communications Commission (FCC).............. 279...
  • Page 6 19.3 Disposal of waste electronic equipment............... 281 20 Appendix.......................... 282 20.1 Legal notes........................ 282 List of figures ........................ 286 List of tables.........................  291 Contacts.......................... 294 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 7: Introduction

    [} page 152] updated. Section Configuring the fieldbus and defining the signals [} page 162] updated. Chapter Isolated application execution with Docker [} page 215] updated. 2019-07-05 Section Technical data NIOT-E-TPI51-EN-RE [} page 275]: Ratings added for UL- conform usage. Table 1: List of revisions Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) ©...
  • Page 8: Brief Description

    OPC UA and MQTT functions address objects in IoT-capable field devices or in the cloud via standardized IoT protocols. The Hilscher netIOT Service offers additional software packets to extend the Edge Gateway base functions by further applications or accesses to specific clouds.
  • Page 9 To accomplish this, Docker uses special techniques from virtualization of operating systems. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 10: Device Drawings

    Positions of the interfaces APL SYS LED1 LED2 ACT POW Fieldbus LINK Rx/TX LINK Rx/TX Top view Front view Bottom view Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 11: Dimensions

    Real-Time Ethernet connectors [} page 12] (11) +24 V DC supply voltage connector (Mini Combicon) Power supply [} page 12] (12) Cover at bottom of device (bolted) Table 2: Positions of the interfaces of NIOT-E-TPI51-EN-RE Dimensions APL SYS LED1 LED2 ACT POW Fieldbus LINK Rx/TX...
  • Page 12: Connectors And Mounting

    The Edge Gateway has 4 USB connectors (4 x USB 2.0), positions (see section Positions of the interfaces [} page 10]). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 13: Wi-Fi

    If you want to use it, find an example docker image with activated HDMI interface and desktop at https:// hub.docker.com/r/hilschernetpi/. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 14: Leds

    Positions of the LEDs on the gateway APL SYS LED1 LED2 ACT POW Fieldbus LINK Rx/TX LINK Rx/TX Figure 3: NIOT-E-TPI51-EN-RE LED positions Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 15: Gateway Status Leds

    100 MBit MBit network connection Position in the device (green) drawing 10 MBit or no network connection (off) Table 5: LEDs LAN interface Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 16: Leds Of The Profinet Io Device Interface

    "on" for approximately 50 ms, followed by "off" for 50 ms. The indicator turns on and off in irregular intervals to indicate low Ethernet activity. Table 7: LED state definitions for the PROFINET IO-Device protocol Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 17: Leds Of The Ethernet/Ip Adapter Interface

    (yellow) dependent) The device does not send/receive Ethernet frames. (off) Table 8: LED states for the EtherNet/IP Adapter protocol Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 18: Table 9: Led State Definitions For The Ethernet/Ip Adapter Protocol

    50 ms. The indicator turns on and off in irregular intervals to indicate low Ethernet activity Table 9: LED state definitions for the EtherNet/IP Adapter protocol Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 19: Commissioning The Edge Gateway

    Read section Using the web browser to establish a connection with the Edge Gateway [} page 20] to find out how to access the Edge Gateway. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 20: Using The Web Browser To Establish A Connection With The Edge Gateway

    You can now use the Edge Gateway manager to configure the device. For this purpose, read section Edge Gateway Manager web page [} page 23]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 21: Access To The Edge Gateway In The Windows Network Environment

    You can now use the Edge Gateway manager to configure the device. For this purpose, read section Edge Gateway Manager web page [} page 23]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 22: Edge Gateway Manager

    Figure 7: Edge Gateway Manager Note: Remember that the secured HTTPS protocol is used here, not the widely spread HTTP protocol. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 23: Edge Gateway Manager Web Page

    Opens the Edge Gateway documentation stored in the device. Opens the homepage of the Device Information Portal in the Internet. Requires a connection to the Internet. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 24: Table 10: Starting Applications With The Edge Gateway Manager

    Function Opens the homepage of the netIOT platform in the Internet. Requires a connection to the Internet. Opens the Hilscher homepage in the Internet. Requires a connection to the Internet. Table 10: Starting applications with the Edge Gateway Manager Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) ©...
  • Page 25: Control Panel

    Ø Enter your user name and your password. Ø Click at Login. ð The Control Panel will be displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 26: First Login

    Ø Enter the new administrator password. It must have at least 7 characters. For reasons of safety, Hilscher recommends using significantly more characters. A strong password consists of upper and lower case letters, digits and special characters. A quality indicator in the dialog box evaluates the password.
  • Page 27: Secure Connection

    As standard, Edge Gateways contain a certificate issued by Hilscher that is not on the list of the known authorized issuers of certificates. Due to that, the browser signals an insecure connection and requests the confirmation to continue.
  • Page 28: Figure 9: Security Error Message Of The Internet Explorer

    Ø To define an exceptional rule that enables the display of the user interface without repeated error messages, click Add Exception. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 29: Figure 12: Firefox Dialog Box: Adding Exceptional Safety Rule

    Ø To save the rule, click Confirm Security Exception. ð When you open the control panel in future, security messages will no longer be displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 30: Figure 13: Security Error Message Of Google Chrome (1)

    Figure 14: Security error message of Google Chrome (2) Ø In order to continue, click at Proceed to ... (unsafe). ð The Control Panel is displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 31: Overview And Main Menu

    Displaying the permissions of the user. User profile [} page 81] Session > Logout Logout Logout [} page 82] Table 11: Functional overview of the Control Panel Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 32 If there is read but no write access right present, this has the following implications: The error message Permission denied is displayed when trying to · make a change. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 33: System Information And System Time

    System info Description Hardware ident. Serial number of the Edge Gateway Model name Model designation of the Edge Gateway (NIOT-E-TPI51-EN-RE) Firmware version Complete version designation of the firmware stored in the Edge Gateway System time Synchronization status of the internal clock of the Edge Gateway.
  • Page 34: Table 13: Info Center: Area Monitoring

    Table 14: Info Center: Area Temperature If the data of the area Monitoring cannot be read, this is grayed out. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 35: License Manager

    To open the Details window: Ø Click at the info button on the left edge of the line (within column Details). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 36: Figure 18: License Information In Window Details

    Ø Hilscher creates an individual license file for your Edge Gateway according to the information supplied by you. Ø Hilscher sends this file back to you as an attachment within the answer e-mail. Consequently, this license file has to be transferred into the Edge Gateway as described in section How to transfer a license into the device? [} page 37].
  • Page 37: Figure 19: Message After The Transfer Of The License File Into The Edge Gateway

    37/294 8.3.2.3 How to transfer a license into the device? Load the individual license file received from Hilscher from your PC into the Edge Gateway. Do the upload as follows: Ø Open the Control Panel in a web browser. Ø Select System > License Manager.
  • Page 38: Displaying The System Log Files

    So ,for system supervision and safeguarding correct reaction on error situations, the file logging daemon syslogd (or an improved successor of it) runs on every Linux system,. On the Edge Gateways from Hilscher, the widely-spread logging daemon Syslog-ng is used, which had been developped by BalaBit IT Security Ltd.
  • Page 39: Table 15: Numeric Coding Of Facility Value In Priority Pri

    Log alert Clock daemon 16…23 Locally used facilities (local0-local7) Table 15: Numeric coding of facility value in priority PRI Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 40: Table 16: Numeric Coding Of Severity Value In Priority (Pri)

    UTF-8 (if a BOM character has been detected) or otherwise it is ASCII-coded. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 41: Table 17: Assignment Of Parts Of Message Line

    The Edge Gateway is configured for a daily change of the logging file and to keep the files of the last seven days. This procedure is denominated as log rotation. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 42: Setting The System Time

    Gateway afterwards so that all software components in the Edge Gateway take the changed time: System > Reboot. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 43 Synchronized to time server <IP address of the time server>:<Port number of the time server > (<NTP address of the time server>) Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 44: Configure Ports For Http/Https Communication

    HTTP and HTTPS requests only at the above mentioned standard ports. Figure 22: Port settings Protocol Default port HTTP HTTPS Table 19: Default ports Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 45 Clicking at the button Refresh, the currently configured values for the port addresses in the input fields HTTP Port and HTTPS Port are displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 46: Backup And Restore

    Ø Select System > Backup and Restore in the control panel. Ê The following screen is displayed: Figure 23: Backup and recovery Ø Click at Create local backup. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 47: Figure 24: Warning Message

    This means, the backup of system files has been completed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 48: Figure 26: Backup And Recovery

    Figure 26: Backup and recovery Ø Click at Restore from backup. Ê The following recovery dialog is displayed: Figure 27: Recovery dialog Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 49: Figure 28: Security Query Prior To System Recovery From Internal Backup File

    In any way, do not interrupt the power supply of the Edge Gateway during system recovery! Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 50: Figure 29: Backup And Recovery

    Ø Select System>Backup and Restore within the Control Panel. Ê The following screen appears: Figure 29: Backup and recovery Ø Click at Restore from backup. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 51: Figure 30: Recovery Dialog (External Source)

    In any way, do not interrupt the power supply of the Edge Gateway during system recovery! Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 52: Figure 32: Backup And Restore When Backup File Is Present

    ð The local backup is internally deleted. Right of Local backup the text No backup is displayed now instead the name of the former backup. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 53: Rebooting The System

    Take care of the consequences of shutting down and restarting for your network, if you reboot the Edge Gateway. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 54: System Shutdown

    · updates already installed signed packages. Note: You can install packages signed by Hilscher only! Use the package management only when Hilscher requests you to use the package management. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 55: Network

    The IP-address parameters include the IP-address, the subnet mask, the Gateway address, and the IP-addresses of Domain Name Server 1 and 2. Figure 37: Default LAN-configuration Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 56: Table 20: Table Lan: Description Of The Columns And Elements

    Subnet mask Table 20: Table LAN: Description of the columns and elements To save your changes permanently, click Save changes. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 57: Figure 38: Lan Configuration(Cifx0 Activated)

    1 minute. To display cifx0, click Refresh. ð The Ethernet interface cifx0 is activated and can be configured now. Figure 38: LAN configuration(cifX0 activated) Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 58: Configuring Wireless Communication (Wi-Fi)

    Wi-Fi interface (wlan0). MAC address displays the MAC address, if Wi-Fi is activated. Table 22: Wi-Fi Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 59: Figure 41: Wi-Fi Operating Mode: Access Point

    ð The message Wi-Fi Settings are succcessfully changed is displayed. Operating mode Access point Figure 41: Wi-Fi operating mode: Access point Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 60: Table 23: Parameters Of The Operating Mode Access Point

    DHCP server if you have checked the box DHCP server. Table 23: Parameters of the operating mode Access point Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 61: Figure 42: Wi-Fi Operating Mode: Client

    To obtain the DNS server address 1 and 2 from a DHCP server address automatically. through DHCP server Enter the DNS server address 1 and 2. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 62 Ø Click Save changes. ð A security request box appears: Ø Click at OK. ð The Wi-Fi settings are saved. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 63: Field

    · the fieldbus output node to send data to the fieldbus (see section Example 5: Fieldbus output node [} page 152]). Inactive The interface is deactivated. Table 25: Operating mode fieldbus interface Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 64: Configuring Ip Routes

    IP destination addresses outside the Edge Gateway (e.g. on the Internet). Figure 43: Routes Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 65: Table 26: Parameters Of Current Connection Configuration Table

    Indicates whether a DHCP service has been set for the connection. Table 26: Parameters of Current connection configuration table Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 66: Figure 44: Defined Routes

    Ø Click Add button. Ê The table creates a new route with the default destination address 0.0.0.0/0: Figure 45: Create new route Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 67: Figure 46: Define New Route

    Metric field. The lower the number, the higher the priority. Ø Click Save button. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 68: Configuring Firewall

    On this page, you can set individual firewall parameters for each connection/interface of the Edge Gateway separately. Figure 47: Firewall Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 69: Table 28: Parameters Firewall

    "Firmware Recovery" (see section Firmware recovery). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 70: Hostname

    The hostname is saved by clicking at If storing the hostname has succeeded, the following message box is displayed: Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 71: Services

    · expiration date, if the license has a run-time limit. Table 30: Operating and display elements A service can allow you individual settings. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 72: Figure 50: Opc-Ua Server For Edge Settings Within The Control Panel, Page Network>Field

    8.6.1.2 OPC UA Server for Edge Figure 50: OPC-UA Server for Edge settings within the Control Panel, page Network>Field Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 73: Table 31: Parameters Of The Opc Ua Server For Edge

    Anonymous access Anonymous access to the OPC UA Server (not secure) Checked / not checked Passive mode of operation Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 74 Edge Gateway. Ø Click at Stop. Ø Wait for some seconds. Ø Click at Start. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 75: User Management

    Access via REST-API (see Functions of the Edge Server [} page 206]) is also a resource. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 76: Table 32: Access Rights Onto Resources

    No access None Read access only Read Read and write access Read, Write Table 33: Access rights to resources Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 77: Managing User Accounts

    Figure 52: User account page Each user account has a user name, a password, and an assigned role. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 78: Security

    1. Selection list for the certificate type (1): Trusted Certification Authorities or Service certificates 2. File selection area for certificate and key files 3. Certificate Viewer Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 79: Figure 54: Certificate Type Selection List

    On selection of Root Certificates the list structure of the Trusted CA Store in the Edge Gateway is displayed. On selection of Service Certificates a tree structure is displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 80: Figure 55: Certificate Viewer

    For more information on the foundations of asymmetric encryption techniques and public key infrastructure, see sections Asymmetric encryption [} page 244] and Certificates and keys [} page 246]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 81: Help

    · change your E-mail address, and · change your password. · Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 82: Logout

    Prior to accessing the Edge Gateway again, a new login (Specifying user name and password) is necessary. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 83: Node-Red - The Wiring Editor

    The current documentation is available here: http:// nodered.org/docs/. For beginning, read the document Getting Started: http://nodered.org/docs/getting-started/. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 84: Modelling Iot Flows With Nodes

    A node can modify and overwrite data before passing the data on. · A node transports data via the msg object in the JSON format. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 85: Opening Node-Red

    Ø Open the Edge Gateway manager (see Calling the Edge Gateway Manager [} page 22]) Ø In the Edge Gateway manager click on the tile Node-RED. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 86: Figure 61: Node-Red Workspace

    Connection without certificate with Microsoft Internet Explorer [} page 28] Connection without certificate with Firefox [} page 28] Connection without certificate with Google Chrome [} page 30] Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 87: Graphical User Interface

    Expand or collapse the node library (13) Node library (14) Node category (15) Nodes (16) Node filter Table 34: Node-RED user interface Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 88: Figure 63: Node

    The blue circle shows that this node has been changed but not transmitted yet. Output port (if available) Node status (if available) Input port (if available) Table 35: Node elements Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 89: Working With Node-Red

    Ø Use the mouse to drag a node from the library and insert the node in the flow. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 90 Ø Click on Deploy. ð The flow will be deployed from the workspace to the Edge Gateway and activated. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 91: Using Git Hub Repository To Store Flows (Projects)

    Note: For a description of the projects function, see https://nodered.org/ docs/user-guide/projects/. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 92: Menu Deploy

    Ê The menu Deploy opens. Ø Click on the menu command to be executed. Ê The dialog box Confirm Deploy is displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 93 Ø Click on Confirm deploy to deploy the flow to the Edge Gateway and activate it. ð Thus, the flow is activated in the Edge Gateway. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 94: Dashboard

    The register card Dashboard of the Edge Bar is itself divided into three register cards: Layout · Theme · Site · Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 95: Table 38: Areas Of The Dashboard Configuration

    Color selection field „Page Settings“ Theme - is only displayed, if option „Custom“ has been chosen in selection list "Style" Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 96 ð The background color is changed. However, the change will get effective at the next deploy operation. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 97: Figure 65: Dialog "Edit Dashboard Tab Node

    Ø In filed Nav.Menu, you can set whether the tab is visible in the navigation menu (option Visible) or not (option Hidden). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 98: Figure 66: Dialog "Edit Dashboard Tab Node

    ð The dialog Edit dashboard tab node is closed and the tab is removed from the tree structure. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 99: Figure 67: Dialog "Edit Dashboard Tab Node

    Ø You can control via the checkbox Display Group Name whether the name of the group as displayed in the field Name is displayed on the dashboard, or not. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 100: Figure 68: Dialog "Edit Dashboard Tab Node

    ð The dialog Edit dashboard tab node is closed and the group is removed from the tab. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 101 Ø Select the desired settings for your widget. Ø Click at ð The edit dialog is closed and the settings of your widget are stored. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 102 Ø Click at ð The widget is deleted and removed from the group, to which it belonged previously. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 103: Figure 69: Dialog "Edit Link Node

    (right of the name of the according link). ð The dialog Edit dashboard tab node is opened. Figure 69: Dialog "Edit link node" Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 104 Edit link node. ð The dialog Edit link node is closed and the link is adapted according to your specifications. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 105: Figure 70: Dialog "Edit Link Node

    Edit link node. ð The dialog Edit link node is closed and the link is removed from the link list. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 106: List Of Nodes

    Watson IoT serial Output debug link mqtt http response web socket fieldbus s7comm Watson IoT serial Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 107 Analysis sentiment Advanced watch feedparse exec Cloud azureiothub IIoT OPC UA nodes Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 108 Table 39: List of standard nodes Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 109: Mqtt Input Node

    Here you enter the name of the MQTT input node that is displayed at the node in Node-RED and used for identification. Table 40: Parameter MQTT input node Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 110: Figure 73: Dialog Box Mqtt Broker Config Node - Tab Connection

    In this dialog box you can configure the parameters for a connection to an MQTT broker. Figure 73: Dialog box MQTT broker config node – tab Connection Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 111: Figure 74: Dialog Box Mqtt Broker Config Node - Tab Security

    Here you enter the user name for the connection. Password Input field Here you enter the password for the connection. Table 42: Parameters in the tab Security Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 112: Figure 75: Dialog Box Mqtt Broker Config Node - Tab Messages

    2 = Exactly once (Sender and receiver acknowledge the message using additional acknowledge messages) Table 43: Parameters in the tab Messages Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 113: Mqtt Output Node

    Parameters of the MQTT output node This section describes the parameters of the MQTT output node. Figure 77: Dialog box MQTT output node Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 114: Table 44: Parameters Of The Edit Mqtt Output Node

    Message of the MQTT output and input node are identical and described in section MQTT input node [} page 109]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 115: Npix Leds

    ð Now, the parameters of the LED node are configured. Via the node settings area you can access the inputs, outputs and icons. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 116: Serial Rs-232 Send

    Ø Speficy in field Name the name to be displayed at the node. ð Now the area node properties is configured. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 117: Figure 82: Dialogf Window „Edit Serial Port Npix Rs232 Node

    , choose the number of stop bits to be used in serial communication. Possible values are 1 or 2. Here the default is 1. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 118: Table 48: Options For Split Input

    Ø Click at Update in order to store your choice and make it valid. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 119: Serial Rs-232 Receive

    ð Now the area node properties is configured. Via the node settings area you can access the inputs, outputs and icons. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 120: Figure 85: Dialogf Window „Edit Serial Port Npix Rs232 Node

    , choose the number of stop bits to be used in serial communication. Possible values are 1 or 2. Here the default is 1. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 121: Table 50: Options For Split Input

    Ø Click at Update in order to store your choice and make it valid. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 122: Serial Inbound Node Rs-485

    In this context, data means an attribute of a Node-RED object, specificly the attribute payload of the msg object. The following prerequisite applies for using this node: In your Edge Gateway NIOT-E-TPI51-EN-RE an RS-485 interface · module NIOT-E-NPIX-RS485 must have been mounted within the extension module bay located at the bottom of the Edge Gateway.
  • Page 123: Figure 88: Dialog Window „Edit Serial Port Npix Rs485 Node

    Ø Within the selection list Parity(4), choose the parity of the serial communication. Here the default is none. Other values are not supported as the UART interface used in NIOT-E-TPI51-EN-RE does not provide parity support. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) ©...
  • Page 124: Table 52: Options For Split Input

    Ø Click at Update to store your choice and make it valid. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 125 Fast devices (<32ms) sending back data over RS-486 in a request/ response manner might not work with the RS-485 nodes. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 126: Serial Outbound Node Rs-485

    The following prerequisite applies for using this node: · In your Edge Gateway NIOT-E-TPI51-EN-RE an RS-485 interface module NIOT-E-NPIX-RS485 must have been mounted within the extension module bay located at the bottom of the Edge Gateway.
  • Page 127: Figure 91: Dialog Window „Edit Serial Port Npix Rs485 Node

    Possible values are: 7 or 8 bits. Default value is 8 bits. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 128: Table 54: Options For Split Input

    Ø Within the selection list Parity(4), choose the parity of the serial communication. Here the default is none. Other values are not supported as the UART interface used in NIOT-E-TPI51-EN-RE does not provide parity support. Ø Within the selection list Stop Bits(5), choose the number of stop bits to be used in serial communication.
  • Page 129 Fast devices (<32ms) sending back data over RS-486 in a request/ response manner might not work with the RS-485 nodes. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 130: Digital I/O Input Node Dio In

    A digital input/ output module NIOT-E-NPIX-IO must have been mounted within the extension module bay located at the bottom of your Edge Gateway NIOT-E-TPI51-EN-RE behind a cover held by two screws. This module provides four digital inputs and outputs each (the inputs dio in0 ...
  • Page 131: Figure 94: Dialog Window Edit Dio In Node - Node Settings Area

    Via the node settings area you can access the inputs, outputs and icons, if present. Figure 94: Dialog window Edit dio in node - node settings area Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 132: Digital I/O Output Node Dio Out

    A digital input/ output module NIOT-E-NPIX-IO must have been mounted within the extension module bay located at the bottom of your Edge Gateway NIOT-E-TPI51-EN-RE behind a cover held by two screws. This module provides four digital inputs and outputs each (the inputs dio in0 ...
  • Page 133: Figure 97: Dialog Window Edit Dio Out Node - Node Settings Area

    Via the node settings area you can access the inputs, outputs and icons, if present. Figure 97: Dialog window Edit dio out node - node settings area Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 134: Examples For Node-Red

    ð The inject node can send messages to the debug node. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 135 ð The sidebar should display numbers. In the standard default setting, the inject node uses the quantity of milliseconds that have elapsed since January 1st, 1970, as payload. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 136: Example 2: Mqtt Input Node

    Ø To open the edit dialog, double-click on the MQTT input node. Ê The edit dialog for entering the parameters will be displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 137 Ê The dialog box returns to the first edit dialog. Ê Under Server the edit dialog shows the address and the port localhost:1883. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 138 (wire) from the output port of the MQTT node to the input port of the Debug node. ð Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 139 ð The Debug node displays messages of the MQTT input node as soon as the topic Timestamp1 changes. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 140: Example 3: Mqtt Output Node

    Ê The red triangle the MQTT output node is displayed with indicates that the node still needs some more parameters which you have to configure in the following steps. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 141 Ø Click Add. Ê The MQTT broker is configured. Ê The dialog box returns to the first edit dialog. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 142 (wire) from the output port of the Inject node to the input port of the MQTT node. ð Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 143 MQTT broker. If you use this example together with the example MQTT input node, you can display the value of the topic Timestamp1 in the tab Debug. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 144: Example 4: Fieldbus Input Node

    Ø Click the tab Info. Ø Click thefieldbus input node to display its properties and a functional description in the tab Info. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 145 Add new fieldbus interface), click Edit to add a new fieldbus interface. Ê The fieldbus configuration node will be displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 146 Ø Then, double-click the entry 16 receive byte (outputs) in the list of Available IO items. Ê The list of IO items displays 2 PROFINET modules. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 147 Ê Column Tag displays Temperature_1 to Temperature_8. If required, you can adapt the signal names in the column Tag. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 148 Ê The display returns to the edit dialog. 13. Entering names: Ø Under Name enter a node name e.g. MyInput. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 149 ð As soon as the value of the signal changes, the Debug output will display the changed value/s and status information. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 150: Figure 101: Message Of The Fieldbus Input Node (Without Error)

    Set_temperature_2. The value 0 for "Error" indicates that the cyclic PROFINET communication works without problems. Figure 101: Message of the fieldbus input node (without error) Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 151: Figure 102: Message Of The Fieldbus Input Node (With Error)

    The following figure displays a value for "Error" that is unequal to 0, i.e. the PROFINET communication does not work. Figure 102: Message of the fieldbus input node (with error) Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 152: Example 5: Fieldbus Output Node

    1. Inserting the first Inject node: Ø Drag an Inject node from the node library and drop it in the worksheet. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 153 3. Inserting the second Inject node: Ø Drag another Inject node from the node library and drop it in the worksheet. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 154 Ê The red triangle the fieldbus node is displayed with indicates that the node still needs some more parameters which you have to configure in the following steps. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 155 Ø If it is not displayed, you first have to load the firmware for PROFINET IO Device in the control panel via the menu entry Network > Field (in the active mode). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 156 Ê The new Tagname which is part of the entire signal name is now displayed for each module. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 157 Ê The PROFINET configuration and signal definition are saved in the Edge Gateway, but they are not activated yet. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 158 Ø Click Deploy to transmit the nodes, that have so far existed in the editor only, to the device and activate them. ð The flow is activated in the Edge Gateway. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 159 ð Signal Temperature_2 is set to value 2 and transferred to the PROFINET IO Controller. Ø At the PROFINET IO Controller, display the input data in a window. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 160: Configuring And Using The Fieldbus Node

    2. Configuring the fieldbus system (e.g. PROFINET) 3. Defining the signals 4. Configuring the fieldbus output node Table 57: Standard procedure Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 161: Table 58: Configuration Steps

    Configure modules node Fieldbus node (configured) Project > Save Define signals Reconfigure / Update Deploy Table 58: Configuration steps Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 162: Configuring The Fieldbus And Defining The Signals

    Ê The edit dialog Add new fieldbus interface config node will be displayed. 2. Opening the PROFINET configuration Ø Click the square to the right of fieldbus interface Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 163: Figure 105: Dialog Box "Add New Fieldbus Interface Config Node

    Figure 106: Dialog box "Add new fieldbus interface config node" Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 164: Figure 107: Profinet Configuration

    ð The user interface for the fieldbus configuration of the Edge Gateway will be opened in a new browser window: (the example shows the PROFINET configuration) Figure 107: PROFINET configuration Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 165: Figure 108: Available Io Items (Example In Figure: Profinet)

    IO items in einer neuen Zeile angezeigt. Figure 109: IO items (Example: PROFINET) Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 166: Figure 110: Dialog „Add New Fieldbus Interface Config Node

    ð The flow will thus be transmitted to the Edge Gateway, and the new configuration will be applied in the Edge Gateway. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 167: Changing The Existing Fieldbus Configuration

    Ø In the workspace, double-click on the fieldbus node to be changed. It is assumed that the node shown in the examples is preconfigured for PROFINET. Figure 112: Fieldbus_node Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 168: Figure 113: Dialog Edit Fieldbus In Node

    Figure 114: Dialog Edit fieldbus in node Ø Select the interface to be changed (in the example this is cifX0 PROFINET...). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 169: Figure 115: Dialog "Edit Fieldbus Interface Config Node

    Edge Gateway no longer processes the data received. Ø Click Open fieldbus configurator. Figure 116: Button Open fieldbus configurator Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 170: Figure 117: Start Screen Of The User Interface For Fieldbus Configuration Of The Netiot Edge Gateway (The Example In The Figure Shows Profinet)

    [} page 176] and Menu commands [} page 173]. 4. Defining signals Ø If required, adapt the signal definitions as you desire. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 171: Figure 118: Edit Fieldbus Interface Config Node

    ð The flow will thus be transmitted to the netIOT Edge Gateway, and the new configuration will be applied in the Edge Gateway. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 172: Figure 119: Error Message - Firmware Does Not Match

    In such a case, check your settings of the Fieldbus interface and the control panel (menu Network > Field)! Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 173: Configuring Profinet And Defining Signals

    (see Help - Contents [} page 175]), and · display the software version of the configuration GUI (see Help - · Information [} page 175]). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 174: Project - Save

    Ø Select a printer or an output file and set the printing parameters. ð The current configuration and signal definition will be printed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 175: Help - Contents

    To display the version of the PROFINET configuration software of the netIOT Edge Gateway, proceed as follows: Ø Click Help > Info. ð The version will be displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 176: Configuration Tree

    PROFINET IO controller or a stand-alone tool. For this purpose the tools use the DCP protocol. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 177: Figure 122: List Of The Possible Input And Output Modules

    Shows the start address of the module (offset in bytes) in the input- and output data memory. The offset is calculated automatically. Table 61: Contents of the table “IO items” Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 178: Table 62: Controls Of The Table "Io Items

    Enter key. Table 62: Controls of the table “IO Items” Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 179: Figure 124: Selected Io Item (Module) For Which You Define Signals

    Figure 125: List of the signal names of an IO item (module) Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 180: Table 64: Contents Of The Table „Signals

    Enter key. Table 65: Controls of the table „Signals“ Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 181: Table 66: Data Types For Signal Names

    5. You can enter the name for signal_tag or bitlist_signal_tag as described in section Defining signals (procedure) [} page 183]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 182: Figure 126: List Of The Configured Input And Output Modules

    PROFINET configuration. In the next step define the signal names as described in section Defining signals (procedure) [} page 183]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 183 Ø Click Delete selected items. Ê The predefined signal is deleted and you can define your own signals. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 184 6. Defining signals: Ø Repeat steps 1‑5 until you have defined all required signals. ð The signal definition is prepared. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 185 The name in the column Tag is a part of the signal name and is described as Signal_tag or Bitlist_signal_tag in section Structure of the signal names [} page 181]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 186: Figure 127: List Of The Send And Receive Signals

    Table 67: Columns of the table of the send and receive signals You can print the table using Print > Print configuration. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 187: Help

    Page with the contents of the online help (currently empty) Info This page displays the version of the PROFINET configuration software. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 188: Configuring Ethernet/Ip And Defining Signals

    (see Help - Contents [} page 190]), and · display the software version of the configuration GUI (see Help - Information [} page 190]). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 189: Project - Save

    Ø Select a folder and then click Save. Ø Use the saved EDS file to configure the EtherNet/IP Scanner. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 190: Printing The Configuration

    To display the version of the EtherNet/IP configuration software of the netIOT Edge Gateway, proceed as follows: Ø Click Help > Info. ð The version will be displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 191: Figure 129: Ip Settings

    Network mask of Edge Gateway · IP address of the gateway, to which the Edge Gateway is connected within the IP network Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 192: Io And Signal Configuration

    Min_length and Max_length). The lower table (IO items) displays the EtherNet/IP configuration and is empty at the beginning. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 193: Figure 130: List Of The Possible Send And Receive Assemblies

    Do not enter two or more underscores in succession. To open the signal configuration of the respective assembly, double-click any line. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 194: Figure 132: Selected Io Item (Assembly) For Which You Define Signals

    Shows the start address of the assembly (offset in bytes) in the input- and output data memory. The offset is calculated automatically. Table 73: Contents of the table „IO items“ Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 195: Figure 133: List Of The Signal Names Of An Io Item (Assembly)

    (a-z), · numbers (0-9), and the underscore. · Do not enter two or more underscores in succession. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 196: Table 75: Controls Of The Table „Signals

    Real (Floating point ) 32 ≈ -/+ 10 real64 Long real ≈ -/+ 10 Table 76: Data types for signal names Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 197: Figure 134: List Of The Configured Send And Receive Assemblies

    Item“ line has been marked, or before a marked „IO item“ line. Figure 134: List of the configured send and receive assemblies Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 198 If you want to access each single bit, define 16 signals of data type bit each. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 199 5. Defining signals: Ø Repeat steps 1‑5 until you have defined all required signals. ð The signal definition is prepared. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 200 The name in the column Tag is a part of the signal name and is described as Signal_tag or Bitlist_signal_tag in section Structure of the signal names [} page 197]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 201: Signal Definitions Overview

    Table 77: Columns of the table of the send and receive signals You can print this table using Print > Print configuration. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 202: Download Of The Eds File

    Info This page only displays the current version of the EtherNet/IP configuration software. See Help - Information [} page 190]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 203: Edge Server

    The Configuration of the Edge Server [} page 211] 14.1 Function principle The Edge Server is a software component that has been developed by Hilscher and is · executed under the Linux operating system of the Edge Gateway. enables secure and capsuled access from the IT-network to functions ·...
  • Page 204: Figure 136: Edge Server Structure

    Figure 136: Edge Server structure Note: For more information on the protocol HTTPS, see https:// en.wikipedia.org/wiki/HTTPS, on REST APIs, see https:// en.wikipedia.org/wiki/Representational_State_Transfer. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 205: Communication With The Ot-Network

    4. Granting read and right access rights requires administrator rights and is described in section Managing user roles [} page 75]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 206: Functions Of The Edge Server

    For a detailed description of the functions and parameters provided by the netIOT Edge Server API, see http://www.netiot.com/external/stkit-doku/. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 207: Internal Structure Of The Edge Server

    The following figure shows the internal structure of the Edge Server for the Edge Gateways: Figure 138: Internal structure of the Edge Server Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 208: Edge Server Control Center

    Information on the Edge Server · Configuration of the Edge Server · List of services · Scan protocols of field devices Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 209: Service List

    For this service, an error message has been stored. Table 79: Symbols for the state of operation in the service list Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 210 Operating status (displayed as text) · Last information · Version · Description · · Information on the author Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 211: Configuration Of The Edge Server

    Configuration. Ê The configuration screen page displays the settings for the server configuration. Figure 141: Server configuration Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 212: Figure 142: Configuration Of The Scan Settings

    IP-address range, the entered IP-addresses must fall into the range of the cifX0 network and its IP-address. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 213: Figure 143: Correct Configuration Of The Scan Settings

    ð Now, the screen page for the scan settings should look like that: Figure 143: Correct configuration of the scan settings Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 214: Selecting The Protocols To Scan For Field Devices

    Ø To save your settings in the Edge Server, click ð Thus, your scan protocol settings of the field devices are saved. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 215: Isolated Application Execution With Docker

    Docker services. Note: Further information concerning portainer.io can be found at http:// portainer.io. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 216 Note: For more information on containers, see the Docker documentation (https://docs.docker.com/get-started/#prerequisites) and, in particular, its glossary (https://docs.docker.com/glossary/? term=container). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 217: Prerequisites For Working With Docker

    Control Panel as described in Starting, stopping and configuring services [} page 71]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 218: Working With Docker Via The Web Gui

    Ê The status changes from Stopped to Running and the yellow icon at the Docker service within the services list changes to green, see figure. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 219: Figure 145: After The Start Of The Docker-Service Within The Control Panel

    (Starting the portainer.io interface for working with the containers [} page 220]) as subsequently described. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 220: Starting The Portainer.io Interface For Working With The Containers

    Ê The portainer.io login screen will be displayed asking you to enter the username and password of an initial user with administrator rights. Figure 147: Initial call of portainer.io Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 221: Figure 148: Portainer.io - Initial Screen Home (Endpoints)

    2. Additionally, the start page „Home (Endpoints)“ of portainer.io is displayed. Figure 148: portainer.io - initial screen Home (Endpoints) Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 222: Figure 149: View Of Portainer.io Dashboard

    Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 223: Functions For Working With Containers

    Continuing the execution of a container after an interruption Remove Rermoving, i.e. deleting a container Table 80: Functions for working with containers Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 224: Example: Execute Web Server Nginx As A Container

    NGINX Repository having been installed there. The http address of the NGINX Repository is https:// hub.docker.com/_/nginx/. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 225: User Management

    The integrated user management of portainer.io may not be confused with the user management of the control panel. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 226: Figure 152: Portainer.io - Entry Page Home

    Ø Within the darkblue menu on the left side click at Users in the SETTINGS area. Ê The page for the user management within portainer.io is displayed (Users>User Management). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 227: Figure 153: Portainer.io - Page Users > User Management

    The figure shows an example configuration with a user admin being defined with assigned administrator rights and with another user named default_user being defined without any administrator rights. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 228: Figure 154: Portainer.io - Display Of User Details

    (Set slider right of Administrator to position „right“) Change password (Specify password twice in the input fields at New · password und bei Confirm password) Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 229: Registry Management

    Ø Within the darkblue menu on the left side, click at Registries within the SETTINGS area. Ê The page Registries (Registry management) for the registry management in portainer.io is displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 230: Figure 157: Portainer.io - Page Registries (Registry Management)

    Figure 158: portainer.io - Page Registries (Registry-Management), Authentication has been activated Here you can enter the username within field Username and the password within field Password. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 231: Figure 159: Portainer.io - Page Create Registry (Registries > Add Registry)

    ð In case of a URL conflict the message Failure – A registry with the same URL already exists is displayed. In that case choose another URL. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 232: Figure 160: Tile Docker Within The Edge Gateway Manager

    Ø Within the darkblue menu on the left side, click at Registries within the SETTINGS area. Ê The page Registries (Registry management) for the registry management in portainer.io is displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 233: Figure 162: Portainer.io - Page Registries (Registry Management)

    Figure 163: portainer.io - Page Registries (Registry-Management), Authentication has been activated Here you can enter the username within field Username and the password within field Password. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 234: Figure 164: Portainer.io - Page Create Registry (Registries > Add Registry)

    Ø Click at the large blue button Custom registry at the right side. Figure 165: Portainer.io - Page Create registry (Registries > Add registry), Custom registry selected Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 235 ð In case of a URL conflict the messageFailure – A registry with the same URL already exists is displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 236: Figure 166: Portainer.io - Page Registries (Registry-Management)

    Figure 166: portainer.io - Page Registries (Registry-Management) ð The page Registry access (Registries > [Registry name] > Access Management) is being opened: Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 237: Figure 167: Portainer.io - Registry Access

    (Field Name) and the URL (Field URL) of the registry. In area Access management users and teams of users are accepted or rejected. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 238: Stack Management

    Ø Within the darkblue menu on the left side click at Stacks. Ê The page Create Stacks (Stacks > Add Stack) for the stack management in portainer.io is displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 239: Figure 170: Portainer.io - Page Create Stacks (Stacks > Add Stack)

    See section Define access control [} page 240]. 4. Area Actions Here the deployment of the stack can be started. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 240 Select one or more teams right of Authorized teams. This implies, that users or teams have already been defined. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 241: Figure 171: Portainer.io - Creating A Stack Via Web Editor

    It looks like this: Figure 171: Portainer.io - Creating a stack via web editor Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 242: Figure 172: Portainer.io - Area "Upload

    Ø Click at Deploy the stack in area Actions in order to create the stack ð If the stack has been created successfully, an according message is displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 243: Figure 173: Portainer.io - Creating A Stack Using Githib

    Ø Click at Deploy the stack in area Actions in order to create the stack ð If the stack has been created successfully, an according message is displayed. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 244: Public Key Infrastructure

    Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 245: Figure 174: Process Of Asymmetric Encryption

    5. The server decrpyt the message using his private key. 6. Client and server continue its encrypted communication using one new created protected transmitted key (symmetric communication). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 246: Certificates And Keys

    Country or region State Location Table 83: Attributes concerning the issuer and owner of the certificate zum Zertifikats- Aussteller und Zertifikats-Inhaber Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 247: Hierarchy Of Trust

    The display of root certificates in the Control Panel of the Edge Gateway follows this list. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 248: File Formats For Certificate And Key Files

    -----END RSA PRIVATE KEY----- at the end. Ø DChange the file extension *.CER or *.CRT to *.PEM. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 249: Use Cases

    List of included root certificates). Figure 175: Use case 1: Verification of the authenticity of the communication partner (Server) Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 250: Use Case 2: Server Certificates For Edge Gateway Services

    Both files have the PEM file format, see section File formats for certificate and key files [} page 248]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 251 For details about “How to work with the certificates and key files (Upload, Download, Removal, Creation)”, see section Working with server certificates for inbound connections [} page 257]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 252: Use Case 3: Client Certificates For Specific Servers

    Mark the entry xyz_key.pem and then click Copy path. Use the · copied path in the Node-RED node for the path to the private key. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 253 How to work with client certificates, describes section Working with client authentication certificates for outbound connections [} page 265]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 254: Verification Of The Authenticity Of The Communication Partner Using Trustworthy Certificates

    ð The window Certificate Viewer now shows the data of the selected certificate (Structure according to X.509 [} page 246]). Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 255: Upload A Trustworthy Certificate Into The Edge Gateway

    Gateway, it is necessary to consequently perform a reboot of the Edge Gateway [} page 53] for the changes to become effective. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 256: Download Of Certificates From The Edge Gateway Into A File

    Ø If you are really sure not to need the current certificate file any longer, click at Yes. ð The selected certificate file is being removed from the Edge Gateway. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 257: Working With Server Certificates For Inbound Connections

    Edge gateway. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 258: Uploading A A Pair Of Certificate File And Key File For Https Und Opc Ua Server

    RED [} page 83], the Edge Server [} page 203] or the REST API [} page 205] from a file into the Edge Gateway. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 259 After a short delay, a message is displayed indicating that the upload has been completed and the Edge Gateway requires a restart Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 260 After a short delay , a message is displayed indicating that the upload has been completed and the Edge Gateway requires a restart Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 261: Working With Certificates For Https And Opc Ua Server

    Ø Select Save and then click on OK. ð The file is stored in *.pem [} page 248] format. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 262 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 263: Working With Key Files For Https And Opc Ua Server

    To upload a key file into the Edge Gateway, proceed as described in section Step 1: Uploading a key file belonging to a server certificate into the Edge Gateway [} page 259]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 264 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 265: Working With Client Authentication Certificates For Outbound Connections

    Edge gateway. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 266: Uploading A Pair Of Certificate And Corresponding Key File For Client Authentication

    Edge Gateway consequently if you upload a certificate for client authentication from a file into the Edge Gateway. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 267 A message is displayed indicating that the upload has been completed and the Edge Gateway requires a restart. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 268 A message is displayed and informs you, that uploading has been completed and the Edge Gateway requires a restart. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 269: Working With Certificates For Client Authentication

    Ø Select Save and then click on OK. ð The file is stored in *.pem [} page 248] format. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 270 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 271 ð The path is now copied into the Windows clipboard. You can use it within Node-RED to open and configure the corresponding element within Node-RED. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 272: Working With Key Files For Client Authentication

    Edge Gateway, proceed as described in section Step 1: Uploading a key file for client authentication for a specific server into the Edge Gateway [} page 267]. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 273 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 274 ð The path to the key file is now copied into Windows clipboard. You can use it within Node-RED to open and configure the corresponding Node- RED element. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 275: Technical Data

    Display LED display 8 LEDs (2 programmable) Real-time clock Buffering Capacitor buffered, max. 7 days backup, maintenance free Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 276 (Burst) Surge voltage EN 61000-4-5 Tests Shock IEC 60068-2-27 Ea Vibration IEC 60068-2-6 Fc Table 86: Technical data NIOT-E-TPI51-EN-RE Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 277: Technical Data Profinet Io Device

    Reference to stack version V3.9 Table 87: Technical data PROFINET IO RT IRT Device Protocol Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 278: Technical Data Ethernet/Ip Adapter

    CIP Sync Services are not implemented. TAGs are not supported. Reference to stack version V2.10 Table 88: Technical data EtherNet/IP Adapter protocol Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 279: Approvals

    20 cm between the radiator and your body. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 280: Industry Canada (Ic)

    être installé et utilisé avec une distance minimale de 20 cm entre le radiateur et votre corps. Figure 178: IC on the device label Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 281: Decommissioning, Dismounting And Disposal

    As a consumer, you are legally obliged to dispose of all waste electronic equipment according to national and local regulations. Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 282: Appendix

    The manual delivered with the product shall apply. Under no circumstances shall Hilscher Gesellschaft für Systemautomation mbH be liable for direct, indirect, ancillary or subsequent damage, or for any loss of income, which may arise after use of the information contained herein.
  • Page 283 Appendix 283/294 Liability disclaimer The hardware and/or software was created and tested by Hilscher Gesellschaft für Systemautomation mbH with utmost care and is made available as is. No warranty can be assumed for the performance or flawlessness of the hardware and/or software under all application conditions and scenarios and the work results achieved by the user when using the hardware and/or software.
  • Page 284 Additional guarantees Although the hardware and software was developed and tested in-depth with greatest care, Hilscher Gesellschaft für Systemautomation mbH shall not assume any guarantee for the suitability thereof for any purpose that was not confirmed in writing. No guarantee can be granted whereby the...
  • Page 285 The customer hereby expressly acknowledges that this document contains trade secrets, information protected by copyright and other patent and ownership privileges as well as any related rights of Hilscher Gesellschaft für Systemautomation mbH. The customer agrees to treat as confidential all of the information made available to customer by Hilscher Gesellschaft für...
  • Page 286: List Of Figures

    List of figures Figure 1: Edge Gateway communication structure.............. Figure 2: Dimensions......................11 Figure 3: NIOT-E-TPI51-EN-RE LED positions ..............14 Figure 4: Gateway state LEDs..................... 15 Figure 5: Default settings of the Ethernet network connectors ..........19 Figure 6: Device label: Hostname..................20 Figure 7: Edge Gateway Manager..................
  • Page 287 Serial inbound node RS-232 send................ 116 Figure 81: Dialog window Edit serial rs232 node - node properties area ......116 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 288 Figure 121: Note: Name of station................... 176 Figure 122: List of the possible input and output modules ............177 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 289 Figure 161: portainer.io - entry page Home................232 Figure 162: portainer.io - Page Registries (Registry management) ........233 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 290 Use case 2: Server certificates for Edge Gateway services......... 250 Figure 177: FCC label......................279 Figure 178: IC on the device label ................... 280 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 291 List of tables 291/294 List of tables Table 1: List of revisions ....................... Table 2: Positions of the interfaces of NIOT-E-TPI51-EN-RE ..........Table 3: Power supply connector ..................Table 4: Description of gateway status LEDs ............... Table 5: LEDs LAN interface ....................
  • Page 292 Functions for working with containers..............223 Table 81: Meaning of columns of tab le of all current registries ..........231 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...
  • Page 293 Table 84: Overview use cases....................249 Table 85: Edge Gateway services ..................251 Table 86: Technical data NIOT-E-TPI51-EN-RE ..............275 Table 87: Technical data PROFINET IO RT IRT Device Protocol.......... 277 Table 88: Technical data EtherNet/IP Adapter protocol ............278 Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) ©...
  • Page 294: Contacts

    Phone: +1 630-505-5301 E-mail: info@hilscher.it E-mail: info@hilscher.us Support Support Phone: +39 02 25007068 Phone: +1 630-505-5301 E-mail: it.support@hilscher.com E-mail: us.support@hilscher.com Edge Gateway | NIOT-E-TPI51-EN-RE (Connect) © Hilscher 2017 – 2019 DOC170502UM07EN | Revision 7 | English | 2019-07 | Released | Public...