bits. Form a new polynomial, the result is 1010000000000001 or hexadecimal A001.
② Load all 1s or hexadecimal FFFFs into 16-bit registers.
③ 16-bit register with low-order byte of the first data byte XOR operation, the
results stored in 16-bit register.
④ 16-bit register to the right one. If the overflow bit is 1, go to step 5, otherwise
go to step 6.
⑤ MOR operation is performed on the 16-bit register with the new generator
polynomial and the result is stored in the 16-bit register.
⑥ Repeat step 4 until it is shifted 8 times.
⑦ XOR operation of the next data byte with the low byte of the 16-bit register,
the result is stored in a 16-bit register.
⑧ Repeat steps 4 to 7 until all bytes of data have been XORed with 16-bit
registers.
⑨ 16-bit register is the content of CRC-16.

4.2. Communication protocol address table and description

Relay operation address table, supports read function of code 01 and remote
control function of code 05
Address
Type
00010
RW
00011
RW
Digital address table, supports read function of code 02
Address
Type
10100
RO
10101
RO
10102
RO
10103
RO
System information address table, supports read function of code 03,04 and
set the code 06,10
RL1
RL2
DI1
DI2
DI3
DI4
IM300 Intelligent Power Monitoring Instrument
Name
Name
64
Register
1
1
Register
1
1
1
1