Note 1: In the 3-phase 3-wire system, the data in 40104 ~ 40107 and
40119~40130 are invalid and value is 0.
Note 2: The correspondence between the above data (Ai) and the actual
value is:
Voltage: U = (Ai / 10) × (PT1 / PT2), Ai is an unsigned integer, unitV.
Current: I = (Ai / 1000) × (CT1 / CT2), Ai is an unsigned integer,
unit:A.
Zero-sequence current: In = (Ai / 1000) × (CT01 / CT02), Ai is an
unsigned integer, unit:A.
Active power: P = Ai × (PT1 / PT2) × (CT1 / CT2), Ai signed integers,
unit:W.
Reactive power: Q = Ai × (PT1 / PT2) × (CT1 / CT2), Ai signed
integers, unit:var.
Apparent power: S = Ai × (PT1 / PT2) × (CT1 / CT2), Ai is an
unsigned integer, unit:VA.
Power factor: PF = Ai / 1000, Ai denote signed integers, no unit.
Frequency: F = Ai / 100, Ai as an unsigned integer, unit:Hz.
energy address table, supports read function of codes 03, 04 and set function
of code 10.Only support writes continuously
Address
Type
40200
RW
Active power of phase B(Wb)
Active power of phase C(Wc)
Reactive power of phase A(Qa)
Reactive power of phase B(Qb)
Reactive power of phase C(Qc)
Apparent power of Phase A(Sa)
Apparent power of phase B(Sb)
Apparent power of phase C(Sc)
The absolute value of total active energy
IM300 Intelligent Power Monitoring Instrument
Data Definition
68