Active power: P = Ai × (PT1 / PT2) × (CT1 / CT2), Ai signed integers,
unit:W.
Reactive power: Q = Ai × (PT1 / PT2) × (CT1 / CT2), Ai signed
integers, unit:var.
Apparent power: S = Ai × (PT1 / PT2) × (CT1 / CT2), Ai signed
integers, unit:VA.
Power factor: PF = Ai / 1000, Ai signed integers, no unit.
Frequency: F = Ai / 100, Ai as an unsigned integer, unit:Hz.
Voltage and current fundamental value address table, supports read
function of codes 03,04
Address
Type
41300
RO
41301
RO
41302
RO
41303
RO
41304
RO
41305
RO
41306
RO
Note: The above correspondence between the data (Ai) and the actual
value is:
Voltage: U = (Ai / 10) × (PT1 / PT2), Ai is an unsigned integer, unit:V.
Current: I = (Ai / 1000) × (CT1 / CT2), Ai is an unsigned integer,
unit:A.
Zero-sequence current: In = (Ai / 1000) × (CT01 / CT02), Ai is an
unsigned integer, unit:A.
Important electrical parameters quick reading address table, supports reads
function of codes 03,04
Address
Type
42000
RO
Fundamental RMS of phase A voltage
Fundamental RMS of phase B voltage
Fundamental RMS of phase C voltage
Fundamental RMS of current Ia
Fundamental RMS of current Ib
Fundamental RMS of current Ic
Fundamental RMS of zero-sequence current In
DI 1
IM300 Intelligent Power Monitoring Instrument
Data definition
Data Definition
88