Minimum value occurrence time of current In
41177
RO
41180
RO
Minimum value occurrence time of total frequency(F)
Minimum value occurrence time of total power factor
41183
RO
(PF)
Minimum value occurrence time of phase A power factor
41186
RO
(PFa)
Minimum value occurrence time of phase B power factor
41189
RO
(PFa)
Minimum value occurrence time of phase C power factor
41192
RO
(PFa)
Minimum value occurrence time of phase A active power
41195
RO
(Wa)
Minimum value occurrence time of phase A reactive
41198
RO
power(Qa)
Minimum value occurrence time of phase A apparent
41201
RO
power(Sa)
Minimum value occurrence time of phase B active power
41204
RO
(Wb)
Minimum value occurrence time of phase B reactive
41207
RO
power(Qb)
Minimum value occurrence time of phase B apparent
41210
RO
power(Sb)
Minimum value occurrence time of phase C active power
41213
RO
(Wc)
Minimum value occurrence time of phase C reactive
41216
RO
power(Qc)
Minimum value occurrence time of phase C apparent
41219
RO
power(Sc)
Minimum value occurrence time of total active power
41222
RO
(W)
Minimum value occurrence time of total reactive power
41225
RO
(Q)
Minimum value occurrence time of total apparent power
41228
RO
(S)
Note: The above correspondence between the data (Ai) and the actual
value is:
Voltage: U = (Ai / 10) × (PT1 / PT2), Ai is an unsigned integer, unit:V.
Current: I = (Ai / 1000) × (CT1 / CT2), Ai is an unsigned integer,
unit:A.
Zero-sequence current: In = (Ai / 1000) × (CT01 / CT02), Ai is an
unsigned integer, unit:A.
IM300 Intelligent Power Monitoring Instrument
87