7.4.5 Gen-set name - reading
Request: 01 03 0B B8 00 08 C6 0D
01
03
0B B8
00 08
0D C6
Response: 01 03 10 49 47 53 2D 4E 54 00 00 00 00 00 00 00 00 00 00 D7 6A
01
03
10
49 47
53 2D
4E 54
00 00
00 00
00 00
00 00
00 00
6A D7
IGS-NT Communication Guide
= Controller address
= Modbus function code
(Read Multiple Registers (page
= Register address: Register number (43001) – 40001 = 3000 DEC =>
BB8 HEX
= Number of registers (43001 - 43008) = 08 DEC => 08 HEX
=
Check field calculation (page 143)
= Controller address
= Modbus function code
(Read Multiple Registers (page
= Length of read data in Bytes (in HEX)
= Object data value (IG)
= Object data value (S-)
= Object data value (NT)
= Object data value (_ _)
= Object data value (_ _)
= Object data value (_ _)
= Object data value (_ _)
= Object data value (_ _) =.> gen-set name is IGS -NT
=
Check field calculation (page 143)
133))
(write LSB MSB !)
133))
98