7.1.6 Ethernet cable

It is recommended to use standard UTP or STP cable with connectors RJ 45. Maximal length of cable is 100 m.
For direct connection between Controller and PC is necessary to use cross-wired cable (only in case that your
PC does not have automatic recognizing of direct and cross-wired cable).

7.2 SMS Message command

7.2.1 Controller address

InteliGen/InteliSys Access code is 15 characters length string. Access code is separated
from controller address by column.
#5:X
Syntax:
X ... controller access code up to 15 characters length
#5:accesscode
Example:
Message is addressed to controller with address 5 and its access code is set to value
'accesscode'.

7.2.2 Access code

Controller address is unique controller identification number located in setpoint group Basic setting : Contr addr
[1 to 32].
Syntax:
Example:
IGS-NT Communication Guide
Image 7.1 Cross-wired UTP 10/100Mbit cable
#XX
XX ... controller address [1 to 32]
#5
Message is addressed to controller with address 5.
85