7.4.11 Remote Switch 1-8 – Set (Remote Control 1-8)
Request: 01 10 18 D6 00 03 06 00 20 00 00 00 1A 7C 9A
01
10
18 D6
00 03
06
00200000
001A
9A 7C
Response: 01 10 18 D6 00 03 67 50
01
10
18 D6
00 03
50 67
IGS-NT Communication Guide
= controller address
= Modbus command
= Register address: Object for engine commands
(46359) – 40001 = 6358 DEC => 18D6 HEX
= number of Modbus registers
= data length in bytes (08F70000+001A)
= argument for RemoteSwitch1-8
IGS-NT (page
72))
= command number
(Commands for IGS-NT (page
72)), command = 26 DEC = 001A HEX
= CRC (write LSB MSB !)
= Controller address
= Modbus command
= Register address
= Release value, number of written Modbus registers
=
Check field calculation (page 143)
(Commands for