User & Password - In One Step; Start The Engine - In One Step - ComAp InteliSys NTC Basebox Communications Manual

Hide thumbs Also See for InteliSys NTC Basebox:
Table of Contents

Advertisement

Note: Before entering the password for writing it is necessary to define user identification number. It is
recommended to enter user identification number and password simultaneously. Entered password stays valid
5 minutes after the last successful writing.
7.4.14 User & Password – in one step
Request: 01 10 18 DA 00 02 04 00 00 00 00 D4 8C
01
10
18 DA
00 02
04
00 00 00 00
8C D4
Response: 01,10,18,DA,00,02,66,93
01
10
18 DA
00 02
93 66
7.4.15 Start the engine – in one step
To start the engine it is necessary to enter an appropriate user and his password first to enable commands, if
these are protected by level 1-7.
Request: 01 10 18 D6 00 03 06 01 FE 00 00 00 01 95 53
01
10
18 D6
0003
06
01FE0000
IGS-NT Communication Guide
= controller address
= Modbus command
138))
= Register address: Object (46363) – 40001 = 6362
DEC => 18DA HEX
= number of Modbus registers (user & password)
= data length in bytes (00 00 00 00)
= User identification "00 00" & password "00 00"
=
Check field calculation (page 143)
MSB !)
= Controller address
= Modbus command
= Register address
= number of written Modbus registers
=
Check field calculation (page 143)
= controller address
= Modbus command
(Write Multiple Registers (page
= 6538 object for engine commands (46359) – 40001 = 6358 DEC => 18D6
HEX
= number of Modbus registers
= data length in bytes (01FE0000+0001)
= argument for Engine start
(Write Multiple Registers (page
(Commands for IGS-NT (page
(write LSB
138))
72))
106