5.5.3 I-CR-R indication and diagnostic LEDs
LED
State
Lights
PWR
Dark
Lights
Slow
RUN
flash
Fast
flash
Lights
CONTR
Flashes
Lights
EMS
Flashes
CAN CONTR
Flashes
(TxC, RxC)
CAN EMS
Flashes
(TxC, RxC)
COM
Flashes
(TxD, RxD)
6 back to Controller setup
5.6 Commands for IGS-NT
First it is necessary to enter an appropriate user and his password first to enable commands, if these are
protected by level 1-7.
IGS-NT Communication Guide
If all other LEDs except of the PWR LED are dark the FW is located in a wrong
type of module; please make sure that I-CB/CAT GAS HW is present
If all LEDs are dark there is no power supply to the module
Firmware is OK and running
Firmware corrupted (periodic Watchdog reset)
RS485 was interrupted or no master found on RS485 backup bus; (controller
with address 1 must be presented in the system to make backup bus working)
Local CAN bus is running OK (between controller and I-CR-R)
No controller detected on local CAN bus; on local bus, speed 32C is always
expected (short connection only – within the switchboard)
Communication on CAN bus between I-CR-Rs is running
CAN bus between I-CR-Rs was interrupted
Automatic speed detection 32C / 8C; enters this mode if no
controller/transmission detected on Primary intercontroller bus (for 2 s)
Local CAN interface activity
Primary intercontroller CAN interface activity
Backup intercontroller RS485 interface activity
Function
72