7.4.13 User & Password – in two steps
Request: 01 06 18 DA 00 00 AE 91
01
06
18 DA
00 00
91 AE
Response: 01 06 18 DA 00 00 AE 91
01
06
18 DA
00 00
91 AE
Request: 01 06 18 DB 00 00 FF 51
01
06
18 DB
00 00
51 FF
Response: 01 06 18 DB 00 00 FF 51
01
06
18 DB
00 00
51 FF
IGS-NT Communication Guide
= controller address
= Modbus function code
(Write Single Registers
(page
137))
= Register address: Object for user identification
(46363) – 40001 = 6362 DEC => 18DA HEX
= ID of user; Administrator = 00 => 0000
=
Check field calculation (page 143)
!)
= Controller address
= Modbus command
= Register address
= Release value
= CRC
= controller address
= Modbus function code
(Write Single Registers
(page
137))
= Register address: Object for entering password
(46364) – 40001 = 6363 DEC => 18DB HEX
= Password = 00 => 0000
=
Check field calculation (page 143)
!)
= Controller address
= Modbus command
= Register address
= Release value
=
Check field calculation (page 143)
(write LSB MSB
(write LSB MSB