M800/M80/E80 Series Maintenance Manual
4 Failure Diagnosis
4.13 IP Address Resetting Procedure at Disabled Network Communication
[M800W/M80W Series Only]

4.13.1 Connectable Control Unit IP Address List Screen

After NC starts, when the communication between the control unit and the display unit cannot be established even after the
time-out time passes, the connectable control unit IP address list screen appears. The contents of IP address list screen is
displayed in English.
If no IP address is displayed, check whether there are any loose or disconnected cables, hardware breakdowns, etc.
(1)
(2)
(3)
Display Items
Display Items
(1)
Connect NC address
(2)
PC IP address
PC Subnet
PC Gateway
(3)
IP address
(4)
System Version
(5)
Serial No.
(*1) Up to ten lines are displayed at a time. When the display item exceeds ten lines, the following lines can be displayed
with the Page down key.
NC Communication Error
Connect NC address: 192.168.100.1
PC IP address
: 192.168.100.2
PC Subnet
: 255.255.255.0
PC Gateway
: 192.168.100.1
IP address
System Version
10.97.37.86
XXX-XXXXXXXX-XX
This displays IP address of the connection destination control unit.
This displays IP address, subnet mask, gateway settings.
This displays IP address of the connectable control unit. (*1)
This displays system version of the connectable control unit. (*1)
This displays serial No. of the connectable control unit. (*1)
Serial No.
XXXXXXXXXXX
Description
129
(5)
(4)
IB-1501273-F