Operation options

7.1

Operation with an operating menu

7.1.1
IO-Link information
IO-Link is a point-to-point connection for communication between the measuring device and
an IO-Link master. The measuring device features an IO-Link communication interface type 2
with a second IO function on pin 4. This requires an IO-Link-compatible assembly (IO-Link
master) for operation. The IO-Link communication interface enables direct access to the
process and diagnostic data. It also provides the option of configuring the measuring device on
the fly.
Physical properties of the IO-Link interface:
• IO-Link specification: version 1.1
• IO-Link Smart Sensor Profile 2nd Edition
• SIO mode: yes
• Speed: COM2; 38.4 kBaud
• Minimum cycle time: 6 msec.
• Process data width: 16 bit
• IO-Link data storage: yes
• Block parameterization: yes
• Device operational: The measuring device is operational 1 second after the supply voltage is
applied.
7.1.2
IO-Link download
http://www.endress.com/download
• Select "Software" as the media type.
• Select "Device Driver" as the software type.
Select IO-Link (IODD).
• In the "Text Search" field enter the device name.
https://ioddfinder.io-link.com/
Search by
– Manufacturer
– Article number
– Product type
7.1.3
Structure of the operating menu
The menu structure has been implemented according to VDMA 24574-1 and complemented
by Endress+Hauser-specific menu items.
For an overview of the operating menu, see the "Overview of the operating menu" section.