Post-Connection Check - Endress+Hauser Liquiphant FTL33 IO-Link Operating Instructions Manual

Point level switch for liquids in the food sector
Hide thumbs Also See for Liquiphant FTL33 IO-Link:
Table of Contents

Advertisement

Electrical connection
Maximum safety
Terminal assignment
Function monitoring
When both outputs are connected, the MIN and MAX outputs assume opposite states (XOR)
when the device is operating fault-free. In the event of an alarm condition or a cable break,
both outputs are de-energized. This means that function monitoring is possible in addition to
level monitoring. The behavior of the switch outputs can be configured via IO-Link.
Connection for function monitoring using XOR operation
Terminal assignment
2 1
3 4
+
6.4

Post-connection check

Are the device and cable undamaged (visual inspection)?
Does the supply voltage match the specifications on the nameplate?
If supply voltage is present, is the green LED lit?
With IO-Link communication: is the green LED flashing?
22
2 1
3 4
+
MAX output
ye2
+
+
+
MAX output
LED yellow
(ye) 2
A0037918
2
2
2
Liquiphant FTL33 IO-Link
LED yellow (ye) 2
+
2
+
2
LED
MIN output
yellow
(ye) 1
ye1
A0037919
+
4
+
4
+
4
ye2
A0037918
LED red
(rd)