Function Test With Test Magnet; Commissioning With An Operating; Menu - Endress+Hauser Liquiphant FTL33 IO-Link Operating Instructions Manual

Point level switch for liquids in the food sector
Hide thumbs Also See for Liquiphant FTL33 IO-Link:
Table of Contents

Advertisement

Liquiphant FTL33 IO-Link
10.3

Function test with test magnet

WARNING
L
Risk of injury!
Ensure that no dangerous processes are triggered in the system.
To perform a function test, hold the test magnet against the marking on the nameplate (for at
least 2 seconds). This inverts the current switching status and the yellow LED changes state.
When the magnet is removed, the switching status valid at that time is adopted.
 13
Test magnet and marking
The test magnet is not included in the scope of delivery and can be ordered as an
optional accessory (see "Accessories" section).
10.4
Commissioning with an operating menu
If an existing configuration is changed, measuring operation continues! The new or modified
entries are only accepted once the setting has been made.
Parameter changes are not accepted until after the parameters have been downloaded.
If using block configuration, parameter changes are accepted only after the parameters have
been downloaded.
WARNING
L
Risk of injury and damage to property due to uncontrolled activation of processes!
Make sure that downstream processes are not started unintentionally.
Endress+Hauser
Commissioning
A0020960
33