Connecting The Device - Endress+Hauser Liquiphant FTL33 IO-Link Operating Instructions Manual

Point level switch for liquids in the food sector
Hide thumbs Also See for Liquiphant FTL33 IO-Link:
Table of Contents

Advertisement

Liquiphant FTL33 IO-Link
6.3

Connecting the device

WARNING
L
Risk of injury from the uncontrolled activation of processes!
Switch off the supply voltage before connecting the device.
Make sure that downstream processes are not started unintentionally.
WARNING
L
Electrical safety is compromised by an incorrect connection!
In accordance with IEC/EN61010 a separate circuit breaker must be provided for the
device .
Voltage source: Non-hazardous contact voltage or Class 2 circuit (North America).
The device must be operated with a 500 mA fine-wire fuse (slow-blow).
Protective circuits against reverse polarity are integrated.
Pin 1 Supply voltage +
Pin 2 1st switch output
Pin 3 Supply voltage -
Pin 4 IO-Link communication or 2nd switch output (SIO mode)
6.3.1
SIO mode (without IO-Link communication)
Minimum safety
Terminal assignment
2 1
3 4
Endress+Hauser
2
1
Q2
3
4
R1
+
L+
C/Q1
L–
MIN output
Electrical connection
IO-Link
SIO
LED yellow (ye) 1
+
4
+
4
A0037916
ye1
A0037919
21