Exporting Compact Field Unit With Pa Slaves From Paa To Pcs 7; Exporting Et 200 I/O Modules From Paa To Pcs 7 - Siemens SIMATIC PCS 7 Operating Manual

Plant automation accelerator 3.0
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

17.9

Exporting Compact Field Unit with PA slaves from PAA to PCS 7

Requiremens
Compact Field Unit (CFU) with PA slaves is created in PCS 7 project.
Procedure
1. In the menu bar, select the "Plugins > Automation > PCS 7 interface > Import / Export
PCS 7" command.
2. Select the "Export" tab.
See also chapters Exporting the hardware configuration (Page 170) and Creating the
Compact Field Unit (CFU) (Page 111).
Result
The CFU with PA slaves is exported to the current PCS 7 project.
17.10

Exporting ET 200 I/O modules from PAA to PCS 7

Procedure
1. In the menu bar, select the "Plugins > Automation > PCS 7 interface > Import / Export
PCS 7" command.
2. Select the "Export" tab.
See also chapter Exporting a PAA project (Page 167).
Note
● It is not necessary to create bus and terminal modules to transfer a project with ET 200
family I/O modules from PAA to PCS 7.
● PS, rack and terminal modules are not transferred via AI.
The image below shows the example of ET 200M physical structure.
Plant Automation Accelerator 3.0
Operating Manual, 04/2019, A5E46351208-AA
17.10 Exporting ET 200 I/O modules from PAA to PCS 7
Export from PAA to PCS 7