Switching ORGANIZATION to MANNED/UNMANNED

If you still don't have operating access when starting operation work, the release procedure is
Operating ac-
automatically called up.
cess
· Several systems, autonomous in terms of organization, can be operated from a shared multi-
Which areas are
area terminal. Both areas in a 'Manned' and 'Unmanned' status can be operated.
switched over?
· The 'Operating mode Manned' display flashes when mixed statuses arise.
· You can now either switch just your own area or all areas from 'Manned' to 'Unmanned'.
Proceed as follows to switch from 'Manned' to 'Unmanned' using the function key:
Switching over
with function
key
Step
Alarms
Alarm device
active
Remote alarm
active
Alarm delay
off
26
Building Technologies
Fire Safety
Action
Press button
1
<Premises manned>
Press softkey
2
<Functions for
sel. message ..>
3
EITHER...
(to switch over your own ar-
ea)
Press softkey
<Switch to UNMANNED>
- or -
<Switch to MANNED>
Faults
Alarm device
fault
Remote transmission
fault
System
fault
Result / Comment
Œ
OR...
(to switch over all areas)
Press softkey
<Switch ALL to
UNMANNED>
- or -
<Switch ALL to
MANNED>
softkey
· The new operating mode can be read off
the display from the 'Information' catego-
ry.
· The LED is lit up in the 'Manned' status
· If the
LED flashes, this indicates that
not all areas are in the same status.
Alarm device
off
Remote alarm
off
Detector
test mode
Operating instructions Œ•Ž
Depending
on actual
status
2
Information
Premises
manned
System
on
A6V10225450_b_en_--
2017.09.07
1

Hide quick links: